Alderon Industries Wireless Versa'larm VA01B Panduan Pengoperasian, Pemeliharaan, dan Pemasangan - Halaman 4
Jelajahi secara online atau unduh pdf Panduan Pengoperasian, Pemeliharaan, dan Pemasangan untuk Sistem Keamanan Alderon Industries Wireless Versa'larm VA01B. Alderon Industries Wireless Versa'larm VA01B 6 halaman. 1-zone alarm
Wireless Versa'larm
1-Zone Alarm - Model VA01B
Part Numbers - 7991 and 7992
Operation, Maintenance and Installation Manual
Installation of the Wireless Transmitter and Float Switch Continued
4. Connect the float switch to the wireless transmitter (yellow)
using the screw in quick connect/disconnect (Fig. 6).
CAUTION: Hand tighten only while attaching the float switch to
the wireless transmitter. Overtightening or using tools will cause
irreversible damage to the product.
Installation of the Alarm Panel and Wireless Receiver
1. The maximum line of sight distance between the wireless transmitter and wireless receiver is 3,250 feet (990.6 meters).
Many factors will reduce this range, some of which include: hills, trees, buildings, etc. Before permanently mounting the
alarm panel and wireless receiver (step 3), plug into the intended wall outlet and perform another pretest of the system as
described on page 2 of these instructions. If the alarm activates, disconnect all power sources before proceeding to step 3
for permanent mounting of the alarm panel and wireless receiver.
Note: If the alarm does not activate, choose another wall outlet that is closer to your wireless transmitter. If moving alarm
panel and wireless receiver closer does not work, remove the wireless receiver from the alarm panel and splice cable, add
up to 100 feet maximum of 18 gauge 3-conductor cable. See step 2 example.
2. If normal installation does not work, use example below (Fig. 7) to increase the signal strength. The alarm panel and
wireless receiver must be mounted indoors.
a. Remove the wireless receiver from the alarm panel.
b. Splice the 3-conductor 18 gauge wire to a maximum of 100 feet. Consult factory for further distances.
c. Position the antenna on the wireless receiver to communicate the alarm panel with the wireless transmitter.
Wireless Transmitter
Alarm Systems
Control Panels
Alderon Industries - Hawley, MN | 218.483.3034 | [email protected] | alderonind.com
™
(Fig. 7)
Wireless Receiver
Antenna
Float Switches
Leak Detection Systems
(Fig. 6)
Alarm Panel
3-Conductor Wire
P/N: 101985
Page 4 of 6