aldes 19 452 Panduan Pemasangan, Pengoperasian & Pemeliharaan
Jelajahi secara online atau unduh pdf Panduan Pemasangan, Pengoperasian & Pemeliharaan untuk Kipas angin aldes 19 452. aldes 19 452 4 halaman. Airflow & zone controls constant exhaust grilles
Airflow Adjustment
CEG-II
1
Spread the sides apart to allow
damper to move up and down.
CEG-II Twin
1
Remove the cover.
Location
of Airflow
Clip 1
* Factory Preset ** Slot positions are numbered 1-4.
Note: Other airflows may be obtained by moving the clips to provide a larger or smaller free area surrounding the regulating bulb.
AIRFLOW & ZONE CONTROLS
CEG-II & CEG-II Twin
Constant Exhaust Grilles
READ AND SAVE THESE INSTRUCTIONS
S2
A = 40 CFM
B = 30 CFM
C = 20 CFM
D = 20 CFM
F = 10 CFM
2
Insert the 2 airflow clips
into the numbered
slots.** Depending on the
position, they may go in
diagonally (Ex. 2-1). See
Table 2 for corresponding
models and airflows.
Location
CEG-II Twin
of Airflow
P/N (ID)
Clip 2
19 455 (11019188)
19 457 (11019187)
19 456 (11019191)
19 458 (N/A)
2
Adjust the airflow to the
desired setting. See Table 1
for corresponding models and
airflows.
TABLE 1
Airflow
P/N
Codes
19 451 (collar)
S1
S1
19 453 (wall-mount)
19 452 (collar)
S2
19 454 (wall-mount)
3
Replace the cover.
TABLE 2
Airflow
Position of
CFM (m
/h)
Airflow Clip 1
3
35 (60)*
2-1
45 (75)
X
50 (95)
X
60 (100)*
1-1
70 (120)
X
90 (150)
X
INSTALLATION
OPERATION
MAINTENANCE
ID
11019090
11019094
11019091
11019095
Position of
Airflow Clip 2
1-1
1-1
X
1-1
1-1
X