An example configuration, where there is a 63 A fuse in the input distribution panel, called MAINPANEL. However,
according to the rule in "To connect stations used in IT-Net" on page 9, MAINPANEL is configured with 36 A. (63 /
sqrt(3) = 36).
NOTE: Start the line with the # character to add comments in the nanogrid.ini file.
NOTE: If the 2 phases connected to each EVSE (EV connector), is connected to L1 & L2 on the input terminal, or if they
must be connected to L1 & L3 depends on the type of the charging station. Refer to the manual of the charging station.
[MAINPANEL]
type=aggregatedfuse
# The rating is the actual fuse 63A / sqrt(3) = 36A, this is done as this
# is an IT-net installation.
rating=36
parent=MAINPANEL
[CC2-1]
type=station
parent=MAINPANEL
outlet/size=2
outlet/1/fallback_current=8
outlet/2/fallback_current=8
PhaseRotation=RxT
[CC2-2]
type=station
parent=MAINPANEL
outlet/size=2
outlet/1/fallback_current=8
outlet/2/fallback_current=8
PhaseRotation=SxR
[CC2-3]
type=station
parent=MAINPANEL
outlet/size=2
outlet/1/fallback_current=8
outlet/2/fallback_current=8
PhaseRotation=TxS
10
Monitoring/Verification
To monitor and verify the NANOGRID™ installation through the NANOGRID™ con-
troller web interface
The NANOGRID™ controller web interface has a tool called "GRID UI" that can be used to monitor and verify the
NANOGRID™ installation.
•
Refer to the CGC500 INSTALLATION MANUAL for instructions on how to access the web interface on the CGC500
GRID CONTROLLER.
•
Refer to the CHARGESTORM CONNECTED 2 USER MANUAL for instructions on how to access the web interface on
a CHARGESTORM CONNECTED 2 station.
1.
In the web interface, go to "NANOGRID" in the left menu
2.
Select the "GRID UI" tab.
1
3.
Refer to the definitions in the table for more information about the "GRID UI" tab.
Node name
Identity name of the node.
Rating
Fuse or station rating.
Car assigned
Charging capacity that has been assigned to the station by the NANOGRID™ controller.
This is the maximum charging current that is reported to any connected EV.
Assigned
Charging capacity that has been assigned to the station by the NANOGRID™ controller, per
phase.
Measured
Current draw per phase, reported by the station to the NANOGRID™ controller.
Configuration instructions
2
CTEK E-Mobility AB
3