Clarus ZF-450 Panduan Pemilik - Halaman 14

Jelajahi secara online atau unduh pdf Panduan Pemilik untuk Sistem Penyaringan Air Clarus ZF-450. Clarus ZF-450 20 halaman. Treatment systems

Clarus ZF-450 Panduan Pemilik
CONTAINER
1.
Aeration
The aeration system must be flushed every maintenance
visit. There are two flushing methods: (A) Air flushing and (B)
Water flushing. Air flushing must be done every maintenance
visit. Water flushing may be done if there is a sign of
clogging in the aeration chamber (e.g. abnormal increase in
recirculation flow).
Figure 18
FAUCET
BACKFLOW PREVENTER
BLOWER
(A) Air flushing procedure:
• Make sure the blower is in the aeration mode.
• Make sure a check valve or backflow preventer is present
for water flushing procedure.
• Close gray recirculation valve (2) all the way. (0%)
• Rotate blue aeration valve (1) back and forth from the 0%
to the 100% position several times to flush.
• Set valves (1) and (2) back to the appropriate positions.
(See Recirculation Flow Adjustment, pg. 10)
(B) Water flushing procedure: (See Figure 18)
• Make sure the blower is off.
• Close valve (2) all the way.
• Connect a water line to the aeration line as shown in
Figure 18.
• Gradually open the water faucet and introduce water
into the system.
• Rotate valve (1) back and forth from the 0% to the 100%
position several times to flush.
• Turn off the water, remove the water line, and reconnect
the air line to the blower.
• Set valves (1) and (2) back to the appropriate positions.
(See Recirculation Flow Adjustment, pg. 10)
(C)
Cleaning the recirculation line:
• Make sure the blower is in the aeration mode. If not,
change the mode by pressing the Manual Backwash
button.
• Open the gray recirculation valve (2) to 100%.
• Flush water through the recirculation line for several
seconds.
• Turn off the recirculation by rotating the gray valve
(2) to 0%.
• Make sure the blower is off. Allow the system to
relax for a few seconds.
• Repeat this cleaning method three times.
• A hose or brush can also be used to clean the recirculation
line. See Figure 20.
• Reset the gray valve (2) to its original position.

AERATION CHAMBER CLEANING

HOSE
CLAMP
G.L
EXISTING AIR LINE
TO TREATMENT UNIT
CONTAINER
FAUCET
BACKFLOW PREVENTER
© Copyright 2020. All rights reserved.
2.
Backwash
The backwash system must be flushed every maintenance.
There are two flushing methods: (A) Air flushing and
(B) Water flushing.
maintenance visit. Water flushing must be done if there is
a sign of clogging in the aeration chamber (e.g. abnormal
increase in recirculation flow).
(A) Air flushing procedure:
• Make sure the blower is in the backwash mode.
• Close the gray sludge transfer valve (4) all the way.
• Rotate the red backwash valve (3) back and forth from the
0% to the 100% position several times to flush.
• Set valves (3) and (4) back to the appropriate positions.
(See Backwash System)
Figure 19
BRUSH
• Turn off the water, remove the water line, and reconnect the
airline to the blower.
RECIRCULATION OR BACKWASH PIPE
• Set valves (3) and (4) back to the appropriate positions. (See
Backwash System)
(C) Cleaning the sludge transfer line:
• Make sure that the blower is in the backwash mode. If
not change the mode by pressing Manual Backwash.
• Open the gray sludge transfer valve (4) to 100%.
• Flush water through the sludge transfer line for a few
seconds.
• Repeat this cleaning method three times.
• A hose or brush can also be used to clean the sludge
transfer line. See Figure 20.
• Reset the gray valve (4) to its original position.
• Return the blower to the normal aeration mode. by
HOSE
pressing Manual Backwash.
BLOWER
Figure 20
CLAMP
G.L
EXISTING AIR LINE
TO TREATMENT UNIT
3.
Foam formation
Make sure there is not an excess amount of foam on the
surface. If excessive foam is present it may indicate high
detergent usage. Meet with owners to inform and educate
them concerning excessive use.
4.
Abnormal water level
If the water level exceeds the partition wall, clean the plastic
cage first with a brush, then check for possible clogging in the
filter media section. Clogs may be cleared by using a manual
backwash tool. The manual backwash tool may also be used
to eliminate a clog in the anaerobic chamber media as well.
14
Air flushing must be done every
(B) Water flushing procedure:
(See Fig. 19)
• Make sure the blower is off.
• Close valve (4) all the way.
• Connect a water line to the backwash
airline as shown in Figure 18.
• Gradually open the water faucet and
introduce water into the system.
• Rotate valve (3) back and forth from
the 0% to the 100% position several
times to flush.
BRUSH