INSTALLATION

M
odels can be installed in a 19" rack system.
Units are supplied with add-on brackets for
these applications. The system is
lightweight and can be easily moved. Some
important points to consider when positioning a unit
for operation:
The installation site should maintain an ambient air
temperature of less than 165
environment for the system remains cooler during
operation, there is less stress on the batteries and
the internal electronics.
The air inlets, vents and fan should not be
obstructed or blocked in any way. The more
breathing space the system has, the cooler it
operates.
T H E C O N T I N U O U S P O W E R C O M P A N Y
o
o
F (74
C). When the
Page 10
The air should remain free from excessive dust
and chemical fumes.
The front panel is designed to fit in a standard 19"
rack. This panel fills a 31/2-inch slot. This system
weighs in excess of 25 pounds, front panel
mounting was not intended to support the entire
unit. Rear support brackets are recommended.
Contact the factory if assistance is required in
properly mounting into a rack.
Once a location has been selected and the unit is
installed, it is ready for operation.
Allow at least 8 hours, after the system is first
installed, to fully charge the internal battery to a
maximum state.
!