SPECIFICATIONS
ELECTRICAL
Input
Voltage (Auto-selectable)
Power Factor Corrected
Frequency
Current
Output
Voltage
Frequency
Current
Power
Crest Factor Ratio
(Non-linear load and
less than 5% THD) Typical
Total Harmonic Distortion (THD)
Dynamic Response
Overload
Efficiency (UPS)
Batt Back-up (Full load\Half load)
UPS Protection
ENVIRONMENTAL
Operating Temperature
Humidity
Altitude
Audible Noise
MECHANICAL
Input Inlet (6' Line Cord Provided)
Output (Qty.)
Cooling
Dimensions HxWxD in(cm)
Weight lbs (kg)
S1500-601
~
~
120
or 240
+10%, -20%
(without Battery discharge)
IAW MIL STD. 1399 Sec. 300
50Hz / 60Hz
~
15.6A @ 120V
7.8A @ 240V~
± 3%
~
120
50Hz / 60Hz (software select)
Line Sync (software select)
12.5A @ 100% non linear load
1500VA, 1050W, 0.7pf
@50% Load
Up to 4.8:1
@75% Load
Up to 3.2:1
@100% Load
Up to 2.4:1
3% Typ; 5% Max.
(@100% Non-linear load)
±4% for 100% Step Load
Change,
0.5 Millisecond Recovery Time
110% for 10 Minutes;
200% for 0.5 Seconds
85% Typ.
5min\17min
Input and Output Short Circuit;
Input and Output Overload;
Excessive Battery Discharge
o
o
o
o
32
F to 104
F (0
C to 40
C)
0% to 95% Non-condensing
Sea Level to 10,000 Feet
39-42 dBA at Five Feet
L5-20 Plug(120V~) or L6-15
Plug(240V~) to IEC320
(1) Duplex 5-15R
Low Velocity, Temperature
Controlled Reversible Forced
Air
14.1(36) x 6.9(17.5) x 21(53)
80 (36)
T H E C O N T I N U O U S P O W E R C O M P A N Y
DESIGN
Standard Features
Specifications
MTBF
Typical Recharge Time to
85% Capacity at 100% Load
CONTROLS AND INDICATORS
Visual Indicators
Sequenced LEDs
Single LED
Front Panel Controls
Audible Alarms
RS232 Data Interface (DB-9F)
Open-Collector (DB-9F)
Optional SNMP Interface
Specifications subject to change without notice.
Page 14
Power Factor Corrected, Digital
Regenerative™ On-Line, Sinewave
Inverter Powers Load Continuously
Extended Brownout Protection
Designed for Non-linear Loads
Continuous Operation on
-20%,+12% Line
Automatic Bypass
RS232 Data Interface
Software Selectable Output
Frequency
AC Output Switch
Auxiliary Battery Connector
Optional SNMP Interface
UL60601-1 Design
FCC Class A
IEEE 587/ANSI C62.41
In Excess of 100,000 Hours
8 Hours
Battery Level, Load Level
AC Input, Inverter On, Fault
Fault Silent, AC Output,
Cold Start, Replace Battery
Power On, Cold Start
Fault Silence, Battery Test
AC Output On/Off
Utility Interrupt, Inverter Failure
Overload, Low Battery
Full Interactive, Remote Computer
Monitoring and Control of UPS
Functions.
Compatible with Systems
Enhancement UPS Monitor &
Control Software
Allows Alarm Function Monitoring
Allows Full Control and Monitoring
(RJ45)
Over Network Connection.
7/04