Acorn Engineering SFST-T-OT-CWB-ITG Petunjuk Pemasangan, Pengoperasian, dan Pemeliharaan - Halaman 7
Jelajahi secara online atau unduh pdf Petunjuk Pemasangan, Pengoperasian, dan Pemeliharaan untuk Unit Kontrol Acorn Engineering SFST-T-OT-CWB-ITG. Acorn Engineering SFST-T-OT-CWB-ITG 8 halaman. Sfst series thermostatic mixing valve supply fixture
A C O R N
RECIRCULATING PIPING DIAGRAM:
TYPICAL RECIRCULATION WITH AQUASTAT
HIGH TEMP
FIXTURE RETURN
C
COLD
WATER
SUPPLY
C
SELECT FLOW RATE NECESSARY TO ENSURE MIXING VALVE IS
OPERATING AT AN ASSE 1017 MINIMUM CERTIFIED FLOW RATE.
SEE LITERATURE.
NOTE: TO BALANCE THE SYSTEM, BEGIN WITH DIVERTING 80% OF THE
RETURN WATER TO COLD SIDE OF THE TEMPERING VALVE (20% OF THE
HOT WATER SOURCE). CONTINUE ADJUSTING UNTIL SYSTEM IS FULLY
BALANCED.
A HEAT TRAP IS RECOMMENDED IF THE MIXING VALVE IS ABOVE THE
WATER HEATER.
TYPICAL CONTINUOUS RECIRCULATION
HIGH TEMP
FIXTURE RETURN
C
COLD
WATER
SUPPLY
C
SELECT FLOW RATE NECESSARY TO ENSURE MIXING VALVE IS
OPERATING AT AN ASSE 1017 MINIMUM CERTIFIED FLOW RATE.
SEE LITERATURE.
NOTE: TO BALANCE THE SYSTEM, BEGIN WITH DIVERTING 80% OF THE
RETURN WATER TO COLD SIDE OF THE TEMPERING VALVE (20% OF THE
HOT WATER SOURCE). CONTINUE ADJUSTING UNTIL SYSTEM IS FULLY
BALANCED.
A HEAT TRAP IS RECOMMENDED IF THE MIXING VALVE IS ABOVE THE
WATER HEATER.
Acorn Controls
Division of Acorn Engineering Company
Manual #7802-117-000
HIGH TEMPERATURE
HOT WATER FIXTURES
EXPANSION
TANK
WATER
HEATER
HIGH TEMPERATURE
HOT WATER FIXTURES
EXPANSION
TANK
WATER
HEATER
SFST Installation & Operation Manual
CONTROL
VALVE
T
HEAT
TRAP
CONTROL
VALVE
T
HEAT
TRAP
, A member of Morris Group International
®
LOW TEMPERATURE
HOT WATER FIXTURES
T
C
BALANCING
VALVE
CHECK VALVE
BALANCING VALVE
T
TEMP/PRESSURE GAUGE
C
CIRCULATOR
FLOW DIRECTION
LOW TEMPERATURE
HOT WATER FIXTURES
T
C
BALANCING
VALVE
CHECK VALVE
BALANCING VALVE
T
TEMP/PRESSURE GAUGE
C
CIRCULATOR
FLOW DIRECTION
™
Date: 09/22/17
LOW TEMP
FIXTURE
RETURN
ADJUSTABLE
AQUASTAT
LOW TEMP
FIXTURE
RETURN
Page 7 of 8