Configuration
1. Switching output signals A1 / A12 between the signal
ranges 0...20 mA or 4...20 mA
The range of the outputs can be switched from 0...20 mA to
4...20 mA or vice versa depending on the positions of jumpers
J 202 and J 203 (Fig. 2).
Output signals
A1 / A12
4 ... 20 mA
0 ... 20 mA
2. Communication connector
Connect the communication connector to output A1 or A12
(Figures 5 to 8). Signals are then transferred in both directions
between the hand-held terminal and the transmitter via the
SIRAX B 811.
When using the field output A12, the 250 Ω burden connected
across output A12 in the power supply unit can be switched
in and out of circuit with the aid of jumpers J 204 and J 205
(Fig. 2).
Communication
connected to:
Field output A12*
integrated 250 Ω resistor
in circuit, the burden at measuring
output A1 is reduced 250 Ω
Choice of A1 output signal
range 0/4 ... 20 mA
Voltage across A1 burden: 10 V
Field output A12*
integrated 250 Ω resistor
not in circuit, the burden at
measuring output A1 is not
reduced.
A1 output signal range
4 ... 20 mA only
Voltage across A1 burden: 15 V
Measuring output A1
Output signal range 4 ... 20 mA
Voltage across A1 burden: 15 V
3. Response of the output signals A1 and A12 for a fault in
the measurement/supply circuit
The response of the output signals A1 and A12 can be set with
the aid of switches 1 and 2 on the DIP switch S 201 (Fig. 2).
Response of output signals A1 and
A12 for a short or open-circuit of the
measurement/supply circuit
Linear output signal
Increasing output signal
Decreasing output signal
(with live zero signal only)
Camille Bauer
Power Pack with Additional Functions
Position of jumpers
J 202
J 203
1
1
3
3
Position of jumpers
J 204
J 205
1
1
1
3
3
3
DIP switch S 201
Switch
Switch
1
2
ON
OFF
OFF
OFF
OFF
ON
Data sheet B811-6 Le – 09.07
Plug-in Module SIRAX B 811
Output
Fault
linear
behaviour
0 mA
(with output
4 ... 20 mA)
Break
– 5 mA
(with output
0 ... 20 mA
Approx.
Short-
26 mA
circuit
with output
0/4 ... 20 mA
4. Response of the output contact AF for a fault in the meas-
Response of the output contact AF for a fault in the meas-
urement/supply circuit
The response of the fault signalling relay can be set with the
aid of switches 3 and 4 on the DIP switch S 201 (Fig. 2).
Operating sense of the
fault signalling relay AF
in the event of a fault
Relay energised
Relay de-energised
ON
OFF
Fig. 2. Positions of the DIP switches S 201 and jumpers J 202 to J 205.
* See "Measuring output" in the "Technical data" section.
Output
output
driving
driving
upscale
downscale
(with live-zero
Approx.
only)
115%
of full scale
Approx. 10%
end value
of full scale
end value
e.g. 23 mA
with output
e.g. 2 mA
0/4 ... 20 mA
with output
or
4 ... 20 mA
11.5 V
with output
0/2 ... 10 V
with output
2 ... 10 V
DIP switch S 201
Switch 3
Switch 4
ON
OFF
J203
S201
1
3
1 2 3 4 5 6
J205
1
J202
3
or
1 V
OFF
ON
1
J204
3