2 WIRING DIAGRAM AND DIMENSIONS
2.1 LIST OF CHANGE-OVER SIGNALS
CN1
POWER TERMINAL BLOCK (SWITCH ON SECONDARY)
PIN1
ALTERNATING CURRENT SUPPLY
PIN2
ALTERNATING CURRENT SUPPLY
PIN3
BAND -
PIN4
BAND +
NOTE 1: Power supply and control circuit supply with the same phase
NOTE 2: Twist power cable
CN1
POWER TERMINAL BLOCK (SWITCH ON PRIMARY)
PIN1
ALTERNATING CURRENT SUPPLY (230Vac)
PIN2
PIN3
CONNECT TO 0 VOLTS ON THE SECONDARY OF THE POWER TRANSFORMER
sq.mm)
TO CONTROL LEAKAGE CURRENT TO GROUND
PIN4
ALTERNATING CURRENT SUPPLY (230Vac)
NOTE 1: Power supply and control circuit supply with the same phase
NOTE 2: Twist power cable
CN2
CONTROL CIRCUIT SUPPLY TERMINAL BLOCK
PIN 1
400 Vac ( 0.1A absorption, max)
PIN 2
230 Vac ( 0.1A absorption, max)
PIN 3
0 Vac ( 0.1A absorption, max)
NOTE 1: Power supply and control circuit supply with the same phase
CN3
CONTROLS TERMINAL BLOCK
PIN1
COMMON 0 V PLC (24V DC)
PIN2
IN PRE-HEAT SIGNAL FROM PLC, 24V DC (0V DC) ( 12 mA absorption, max)
PIN3
IN SEALING SIGNAL FROM PLC, 24V DC (0V DC) ( 12 mA absorption, max)
PIN4
IN RESET SIGNAL FROM PLC, 24V DC (0V DC) ( 12 mA absorption, max)
PIN5
IN CALIBRATING SIGNAL FROM PLC, 24V DC (0V DC) ( 12 mA absorption, max)
PIN6
OUT SEALING FAULT (CONTACT N.C.) cosΦ = 1
PIN7
OUT SEALING FAULT (CONTACT N.C.) cosΦ = 0.4 250V 5A
THERMOSALD ISC – MANUAL QUICK START
Manual cod.: 3ES080x_V5.1_QS_EN
Includes all previous models
250V 8A
Page Nr.
3
(4 - 10 sq.mm)
(4 - 10 sq.mm)
(4 - 10 sq.mm)
(4 - 10 sq.mm)
(4 - 10 sq.mm)
(4 - 10 sq.mm)
(4 - 10
(4 - 10 sq.mm)
(1sq.mm)
(1sq.mm)
(1sq.mm)
(1 sq.mm)
(1 sq.mm)
(1 sq.mm)
(1 sq.mm)
(1 sq.mm)
(1 sq.mm)
(1 sq.mm)