Electrical
To be installed per NEC NFPA70 requirements for U.S. installations.
Installation in other regions must conform to local electrical codes. Instructions provided below
are general guidelines and may not cover local requirements.
1. Remove the lid from the A540 junction box.
2. Run conduit to junction box. Ensure conduit has sealing fitting at feeder end if installation is in
hazardous location.
Conduit connection should be sealed from water intrusion through either rubber washers,
caulking, or other sealing means.
3. Pull cable from process controller into A540 junction box.
4. Refer to wiring diagram above, as well as documentation for process controller to properly wire
the process controller to the A540 ground cable.
5. Reinstall lid onto junction box.
6. Designate an ungrounded location to store the ground clamp while not in use. It is critical that
the ground clamp be ungrounded while not in use. Storing in a grounded state can lead to
unsafe loading conditions.
7. Verify proper functionality of system by testing before putting into service.