Dixon BAYCO 6200 Panduan Petunjuk Pemasangan & Pengoperasian - Halaman 2

Jelajahi secara online atau unduh pdf Panduan Petunjuk Pemasangan & Pengoperasian untuk Peralatan Industri Dixon BAYCO 6200. Dixon BAYCO 6200 9 halaman. Drop elbows

Dixon BAYCO 6200 Panduan Petunjuk Pemasangan & Pengoperasian
IMPORTANT: This elbow is designed for use with standard 4" top seal service station
adapters. To properly operate and maintain your BAYCO 6000 / 6200 / 6500 series elbow the
following instructions are provided. Please read with care as improper handling or maintenance
may cause a hazardous condition.
CAUTION: Do not modify your BAYCO 6000 / 6200 / 6500 series elbow for any reason. It
can result in a hazardous condition due to operating difficulties or operation malfunction.
Disassembly or tampering will void the product warranty.
Never smoke or allow an open flame near your dispenser when handling volatile
materials such as gasoline and fuels. An explosion could result. Remember
safety is everyone's business.
Installation: When the Bayco 6000 / 6200 / 6500 elbow is shipped, the sight glass and
gaskets are enclosed in a plastic bag attached to the elbow. These must be installed with
the required mating Bayco inlet (3" or 4" male or female purchased separately). Take the
sight glass and gaskets out of the plastic bag and place one gasket inside the elbow inlet
end and make sure it is sealed evenly. Carefully (keep straight) slide the sight glass into
the inlet end and onto the installed gasket. Place the other gasket inside the inlet and on
the sight glass. Attach the mating inlet using the four socket head cap screws and lock
washers supplied. Coat cap screws with anti-seize compound.
Lubricate Stem: This product has been assembled with anti-seize compound and lubricated
for easy maintenance and trouble-free service. However, we recommend lubricating the
stem through the grease nipple using lithium based or quality automotive type grease
prior to service. It is recommended to apply lubricant to grease nipple, cam arm
bearings, and other moving parts every month. Monthly inspection and lubrication
become mandatory for items that are seldom used. Condensation, rain and road
salts can cause corrosion build-up and binding when product not in use.
Check Operation: 6200 / 6500 elbow: Place elbow bottom end on service station adapter
(elbow is designed for use with 4" top seal adapter only). Move operators handle to the
11 o'clock open/unclamped position. Release and hold the safety latch if equipped with
one. Move the handle clockwise to 2 o'clock position for full clamping (lever cannot be
moved any farther). Check locking arms on adapter. If the elbow is fitted with a safety
latch, make sure the safety latch is fully engaged, preventing movement of operating
handle. Release by moving handle to 11 o'clock. If fitted with safety latch, lift the latch
lever and operating lever at the same time.
6000 elbow with D-handle: Place elbow bottom end on service station adapter. Pulling on
D-handle is not necessary, coupler mechanism is self-engaging; simply push elbow
vertically down onto service station adapter until locking arms pop in. Now push down
on handle to ensure full clamping (handle cannot be moved any farther). Check locking
arms on adapter. Release by pulling on handle until locking arms disengage.
2
090066 R10