VR6000, VR6200 and VR6000 Drop Elbows
Inspection
Drop elbows can fail to operate if not properly maintained. If the
VR6500 / VR6200 / VR6000 elbow develops any problems, remove
from service and contact your Bayco distributor describing the
difficulty. The distributor will provide further instructions for repair and
warranty of the product.
Elbows should be inspected monthly. Check the adapter-to-elbow O-
ring seal and the flange where the base is attached to the elbow body
for any signs of leakage. Change seals if necessary. Check and
tighten all fasteners periodically. Lubricate the lever stem. Check the
bushings and replace if cracked or worn, and change if required.
Check operation as per above.
Regularly replace bushings. Some Bayco elbows contain polymer
bushings, which protect and extend service life of bronze locking
arms. The bushings are designed to wear (instead of bronze arms)
and should be replaced every few months. Operators must be
encouraged to inspect and replace polymer bushings to obtain
maximum elbow performance and longevity.
Optional Accessories
The following are available as optional accessories for VR6200 and
VR6000 elbows:
Safety Latch Kit #6200SLK (VR6200 only)
Installation instructions are included with the items when ordered for
retrofit.
Dixon Bayco Warranty
For complete warranty information, please refer to the latest
Dixon catalog.
4
877.582.3569
VR6500/VR6200/VR6000