4.1 STATUS DISPLAY
4.1.1 POWER INDICATOR
The POWER indicator will flash at a rate of 2Hz when the AC+ line voltage goes below the
drop-out level. It will illuminate steadily when the AC+ line voltage returns above the brown-
out restore level. The indicator will extinguish when the AC+ line voltage is below
approximately 70 Vrms.
4.1.2 CONFLICT INDICATOR
The CONFLICT indicator will be illuminated when a conflicting proceed signal fault is
detected. The Channel Status display will show the active signals for each channel at the
time of the fault and the channels involved in the fault.
4.1.3 RED FAIL INDICATOR
The RED FAIL indicator will be illuminated when an absence of signal (dark signal head) is
detected on a channel(s). The Channel Status display will show the active signals for each
channel at the time of the fault and the channels involved in the fault.
If the Red Enable input is not active the RED FAIL indicator will flash once every two
seconds to indicate that Extended Monitoring functions (Red Fail, Dual Indication, and
Clearance) are disabled.
4.1.4 CVM INDICATOR
The CVM indicator will be illuminated when a Controller Voltage Monitor Fault is detected.
The Channel Status display will show the active signals for each channel at the time of the
fault.
4.1.5 24V-1, 24V-2 VOLTAGE MONITOR INDICATORS
These indicators will be illuminated if the corresponding voltage input is below the minimum
specified level. The Channel Status display will show the active signals for each channel at
the time of the fault.
If the 24V INHIBIT input is active the 24V-1 and 24V-2 indicators will flash once every two
seconds to indicate that Voltage Monitor functions are disabled.
4.1.6 DIAGNOSTIC INDICATOR
The DIAGNOSTIC indicator will illuminate when an internal monitor failure is detected. This
indicator is used to inform the service technician of a monitor hardware and/or firmware
failure.
Due to the nature of these hardware/firmware failures, other fault indicators that may be
concurrently displayed may not be valid.
4.1.7 RP STATUS INDICATOR
The RP STATUS indicator will illuminate when the Recurrent Pulse detection function has
triggered a Conflict, Dual Indication, or Red Fail fault. See Section 2.4.
4.1.8 DUAL INDICATION INDICATOR
The DUAL INDICATION indicator will be illuminated when a Dual Indication fault is
detected on a channel(s). The Channel Status display will show the active signals for each
channel at the time of the fault and the channels involved in the fault.
Eberle Design Inc.
NSM-3E Signal Monitor Unit
Operations Manual
Section 4
Front Panel Description
Page 8