3HS RMS-D II Buku Panduan Instalasi - Halaman 4

Jelajahi secara online atau unduh pdf Buku Panduan Instalasi untuk Alarm Asap 3HS RMS-D II. 3HS RMS-D II 13 halaman. Ceiling mounted visual smoke detector

Installationshandbuch RMS-D II und RMS-V II

Malfunction

The smoke detector shows different malfunctions as follows:
1. Impurities LED switches between red / green
2. Manipulation LED lights yellow permanently
The outlet for "manipulation" will be activated after a delay time of approximately 200s. This signal must
be connected to the fire detector processor and evaluated.
A detector in Error Mode cannot recognize smoke!
For security reasons, the smoke detector can give off an alarm signal for certain malfunctions when the
cause is not removed.
A malfunction can be caused by:
1. Attempted Manipulation.
2. Covering or Taping the Surface.
3. Impurities on the Surface.
4. Insects.
5. Objects within < 1000 mm distance.
6. Direct Blinding or Reflections of Sunlight or Other Bright Lights.
7. Strong Electromagnetic Radiation directly near the smoke detector.
8. Condensation on the Surface.

Alarm

In case of an alarm the display on the smoke detector will light up red and the outlet for "Alarm" will be
activated.
1. The alarm will go off when the particle concentration reaches a set limit.
2. The alarm can also go off when the error signal is set off and not analyzed by the fire detector unit.
Installationshandbuch: RMS-D II und RMS-V II Relais
®3HStrading GmbH&Co.KG, Königsheimer Strasse 13,
D-78603 Renquishausen, Tel. 07429 33 61 Fax. 07429 91 61 335,
www.3HS.de
Seite 4 von 13
Stand: 01.12.2015
Version:2.7