DE-4000 Firmware Download Quick Start Guide
This quick start guide refers to several documents that will provide step-by-step procedures for
programming and downloading the support files for the DE-4000. (This document assumes that you
have exported a JSON file from the DE-4000 before you begin. If there is no configuration file started,
please ignore this.)
WARNING!
Failure to properly follow these instructions may cause damage to the DE-4000 system.
NOTE: Basic understanding of DE-4000 operation and configuration is required. Reference from DE-
4000 OCM at http://www.altronic-llc.com/pdf/annunciators/DE-4000%20OCM%203-20.pdf.
You should have the following documents available for your reference:
ST-Link Procedure _R3.pdf
MicroSD SOM Update.pdf
Change IP Address.pdf
Pinging DE-4000.pdf
HARDWARE REQUIRED: 693225-KT, which includes the following:
Programming cable (Board to Adapter)
Programmer (Used with PC)
Programmer Adapter Board
SOFTWARE REQUIRED: ST-LINK V4.6.0
Please note the ST-LINK software can be downloaded from the Altronic website,
http://www.altronic-llc.com/catalog-downloads.shtml
Please perform the following steps in order:
1. Review document ST-Link Procedure_R3.pdf.
2. Review document MicroSD SOM Update.pdf. Remember, when loading 2.X firmware or
higher, you will be updating an "update.atf" file and a "kernel.atf" file that are located within
the root of the microSD card.
Note: The MicroSD card needs to be 32 GB or less. Larger capacity cards will not work
properly.
3. To properly set your computers IP address, please refer to document Change IP Address.pdf,
set your computer IP address to 98.102.65.200.
under Terminal Programs