Technical data

Differential Pressure controller DPC200-EP500
Measuring range: 500 Pa
Differential Pressure controller DPC200-EP1000
Measuring range: 1000 Pa
Differential Pressure controller DPC200-EP4000
Measuring range: 4000 Pa
Differential Pressure controller DPC200-EP50
Measuring range: 50 Pa
Mounting set M-DS
with screws, bleeders and 2m plastic tube
Measuring medium:
Air or non-aggressive gases
Measuring principle:
Silicon diaphragm with spring and differential transformer
Measuring ranges:
0...50 Pa, 0...500 Pa, 0...1000 Pa, 0...4000 Pa
Overpressure protection: 0,2 bar
Static pressure:
Max. 0,2 bar
Pressure connections:
Hose line ø5 mm and ø6 mm
Case:
Case polyamid, cover ABS
Supply voltage:
15...30 Vdc or 24 Vac ± 15 %
Electronic protection against reversed polarization
Current consumption:
Approx. 10 mA @ 10Vdc; 12 mA @ 24 Vdc
Output:
0...10 V
Display:
LCD-Display, 2x16 characters
Mode:
Measuring mode or controlling mode
Controlling algorithm:
PI algorithm
Setpoints:
2 setpoints adjustable within software,
Setpoints are selectable with floating contact input
Protection class:
IP 54 acording EN 60529
Ambient temperature:
-10...+50 °C
Storage temperature:
-25...+60 °C
Weight:
Approx. 250 g
Mounting:
Vertical, position dependence by turning of 90°: approx. 25 Pa
Interference emmission: According EN 50081-2, EN 50082-2, CE
Influences limits:
Zero error:
Sum of linearity and hysteresis
(depends on measuring range):
Temperature drift, zero point:
Temperature drift, span:
Arthur Grillo GmbH · Am Sandbach 7 · 40878 Ratingen
Telefon 0 21 02 - 47 10 22 · Telefax 0 21 02 - 47 58 82
www.grillo-messgeraete.de · [email protected] · www.sensor-store.de
Order No.
2567
Order No.
2568
Order No.
2569
Order No.
2559
Order No.
25110
± 0,75 %
± 0,5 % ... ± 1 %
± 0,3 % / 10 K
± 0,2 % / 10 K