Function
Input to Output
Follower Mode
Temporal Code 3 Mode
Steady Mode
For the above modes DIP Switch 4 determines which Input controls the
corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by Input 1.
Switch 4 in the OFF position causes output(s) to be controlled by Input 2.
Function
Amseco
Sync Mode*
Faraday
Sync Mode*
Gentex
®
Sync Mode*
Gentex is a registered
trademark of
Gentex Corporation.
®
System Sensor
Sync Mode*
System Sensor is a
registered trademark of
Honeywell.
CooperWheelock
®
Sync Mode*
CooperWheelock is a
registered trademark of
Cooper Wheelock.
*Note: The AL602ULADA, AL602ULADAJ, AL802ULADA, AL802ULADAJ, AL1002ULADA and
AL1002ULADAJ will only synchronize horns, horn/strobes and strobes that contain synchronization capability.
Contact signal manufacturer for more detailed info.
The same synchronization mode must be selected for all outputs.
02 ULADA Application Guide
Output Programming Selection Table:
Outputs must be programmed independently (OUT1 - OUT4)
Switch Positions
ON
OFF
1
2, 3
3
1, 2
1, 2, 3
Sync Mode Selection Table:
Switch Positions
ON
OFF
1, 3,
2
4
2, 4
1, 3
1, 2,
3, 4
1, 2, 4
3
2, 3, 4
1
Descriptions
Output follows signal it receives from the corresponding
input (i.e. FACP Sync module - maintains synchronization
of notification appliance circuit).
Enables Temporal Code 3 signal generation output.
This mode will accept a steady or a pulsing input.
A steady output signal will be generated.
This mode will accept steady or pulsing input.
Descriptions
This mode is designed to work with the Amseco series of horns,
strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the flash timing of the
strobe, and silencing the horns of the horn/strobe combination over
a two-wire circuit while leaving strobes active.
This mode is designed to work with the Faraday series of horns,
strobes, and horn/strobes to provide a means of synchronizing the
Temporal-coded horns, synchronizing the flash timing of the strobe,
and silencing the horns of the horn/strobe combination over a two-
wire circuit while leaving strobes active.
This mode is designed to work with the Gentex
strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the flash timing of the
strobe, and silencing the horns of the horn/strobe combination
over a two-wire circuit while leaving strobes active.
This mode is designed to work with the System Sensor
horns, strobes, and horn/strobes to provide a means of synchroniz-
ing the Temporal-coded horns, synchronizing the one-second flash
timing of the strobe, and silencing the horns of the horn/strobe
combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the CooperWheelock series of
horns, strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the one-second flash tim-
ing of the strobe, and silencing the horns of the horn/strobe combina-
tion over a two-wire circuit while leaving strobes active.