y PRESET: [CHANNEL / GROUP] – Preset
memory for either channel or group
- UP or DOWN used to select value (0-
100%)
- LEFT or RIGHT used to select index
- LEFT (hold) then RIGHT used to select
between channel or group
Note: These presets are held in
memory.
STATUS
Use the STATUS button to scroll through the
different sub menus below:
y DALI BUS POWER: [OK/DALI PSU
PRESENT/NO PSU PRESENT]
y BALLAST
STATUS:
PRESENT]
y LAMP
STATUS:
PRESENT]
y LAMP POWER: [ON/OFF/NOT PRESENT]
y RESET STATE: [YES/NO/NOT PRESENT]
y LIMIT ERROR: [YES/NO/NOT PRESENT]
y VERSION
NUMBER:
UNKNOWN/NOT PRESENT]
y SHORT
ADDRESS:
MISSING/NOT PRESENT]
ADDRESS
y CHANNEL ASSIGN: Used to change the
channel assignment of a ballast
- LEFT or RIGHT to select ballast to
program
- UP or DOWN to select the new channel
index
- YES (and hold) to program ballast
- NO to cancel new channel index (before
programming occurs)
y GROUP ASSIGN: Used to assign a ballast
to a group
- LEFT or RIGHT to select ballast to
program
- UP or DOWN to select the new group
DALI-Scope User Guide
[OK/ERR/NOT
[OK/FAILURE/NOT
[VERSION/
[ADDRESS/
- YES (and hold) to confirm action
- NO to cancel action (before programming
occurs)
y GROUP REMOVE: Remove a group
assignment from a ballast
- LEFT or RIGHT to select ballast to
program
- UP or DOWN to select the group
assignment that is to be removed
- YES (and hold) to confirm action
- NO to cancel action (before programming
occurs)
y SCENE ASSIGN: Store a value for a
scene within the ballast memory
- LEFT or RIGHT to select ballast to
program
- UP or DOWN to change the scene level
- LEFT & RIGHT to select scene index
- YES (and hold) to confirm action
- NO to cancel action (before programming
occurs)
y SCENE REMOVE: Remove a scene value
from the ballast memory
- LEFT or RIGHT to select ballast
- UP or DOWN to change the scene that is
to be removed
- YES (and hold) to confirm action
- NO to cancel action (before programming
occurs)
y AUTO CHANNEL ASSIGNMENT: Assign
short addresses to new ballasts
- YES (and hold) to confirm action
Note: This function is for programming new
ballasts that have not been assigned a channel
number. It will reset ALL ballasts on the DALI
circuit and give them new channel numbers. If
you need to program a new ballast on a circuit
without affecting other ballasts, please isolate
the new ballast.
Page 6