cleaning described in this leaflet, no
other customer servicing of this product
is required. Repairs, when needed, must
be performed by the manufacturer.
7.5 Chamber Cleaning
Cleaning or replacing of the chamber
cover should only be carried out by
suitably trained personal.
1. Remove the Alarm from the mounting
plate.
2. Remove the battery or batteries.
3. With a flat screwdriver unclip the three
cover clip points (see figure 8a).
4. Remove the cover (see figure 8b).
5. Unplug the thermistor by holding the
thermistor PCB and pulling the pins out
of the sockets (see figure 8c).
6. To remove the chamber top turn
the chamber anti-clockwise approx. 15
degrees (see figure 8d).
7. Blow out or use a soft bristled brush to
remove dust and dirt form the chamber
base.
8. Fit a new chamber top and clip in
place by turning clock-wise 15 degrees.
9. Insert the thermistor PCB into the
sockets and ensure the thermistor is
perpendicular to the chamber (see figure
8e).
10. Place the cover back on the Alarm
taking care to ensure the thermistor is
protruding out the cover (see figure 8f).
11. Replace the battery / batteries and
reattach to the mounting plate.
12. Press the test button to ensure the
Alarm is working correctly.
Figure 8a
Figure 8b
Figure 8c
Figure 8d
Figure 8e
Figure 8f
8.6 Smoke Alarm Automatic Self-Test
The smoke chamber in the Smoke
Alarms automatically tests itself every 16
seconds. If the chamber is degraded it
will beep twice every 48 seconds with
2 yellow LED flashes at the same time.
If this happens clean the unit. If the
beeping persists and the beep does
not coincide with a yellow light flash,
return the unit for service (see Section 5 -
Getting Your Alarm Serviced).
10