7
6. After the circuit is checked "dead" and made certain that it is
maintained "dead", connect the remote switch cable and close the
grounding switch from the safest distance.
7. Padlock the ground switch closed by disconnecting the control switch
cable and sliding the cover to the left. It may also be locked by an
optional key lock K3, if provided, Figure 3).
(B) For Cable Testing
1. With the device out of the breaker compartment, correctly identify
Line and Bus Terminals for the Breaker Compartment and visually
make certain that the connections will be made to the Line Terminals.
2. Lift the device and load it on the extension rails of the switchgear
compartment with extreme care.
3. Push the device to the "Test" position as indicated by the crisp clicking
sound of the levering latch engaging the levering nut.
4. Using the breaker levering crank, lever the device to the "Connected"
position as indicated by the red flag appearing in front of and under the
levering crank.
5. Unlock and open the test ports and test for "dead" circuit using
correctly rated neon test stick or equivalent.
I.B. 792A190B