AKO AKO-145601 Panduan Cepat

Jelajahi secara online atau unduh pdf Panduan Cepat untuk Pengontrol Suhu AKO AKO-145601. AKO AKO-145601 2 halaman.

AKO AKO-145601 Panduan Cepat
1456H012 Ed.04
Quick guide
AKO-145601

Quick start

1
Connect the controller according to the diagram in the ''wiring'' section.
2
Configure the rFt, EM and SH parameters according to the indications in the "Start up configuration".
1
Wiring
Emergency
power supply
12 Vdc input
AKO-80077
AKO-145601
Max. 25 m
(AKO-15586)
Probe 1
Temperature
AKO-15606
Probe 2 Suction
pressure
AKO-15571
Red +5V
Green signal
Black Common
2

Initial configuration

Prior to start-up, it is vital to configure the following para-
meters:
RFT: Select the type of refrigerant gas used in the
installation from among the following com-
patible gases:
0: R-22
1: R-134A
3: R-407C
4: R-410A
6: R-23
7: R-507C
9: R-744
10: R-407A
12: R-507A
13: R-245F
EM: Select the expansion valve model installed
from among the following compatible mo-
dels:
1: Danfoss ETS 12.5 / 25B
2: Danfoss ETS 50B
3: Danfoss ETS 100B
4: Danfoss ETS 250
5: Danfoss ETS 400
6: Alco Ex4
7: Alco EX5
8: Alco Ex6
9: Alco EX7
10: Alco EX8 (330 step/sec)
11: Alco EX8 (500 step/sec) 12: Sporlan SEI 0.5~11
13: Sporlan SEI 1.5~20
14: Sporlan SEI 30
15: Sporlan SEI 100
16: Sporlan SEI 175
17: Carel E2V
SK: Configure the overheating set point
Warnings
GB
Using the unit not observing the manufacturer's instructions may alter the appliance's safety requirements. Only probes supplied
by
AKO
should be used for the appliance to operate correctly.
The unit should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does
not exceed the values indicated in the technical data.
For the reading to be correct, the probe should be used in a place without heat influences apart from the temperature you want
to measure or control.
The probe and its cable should
The power supply circuit should be equipped with a switch for its disconnection of at least 2A, 230V, situated near the appliance. The
cables are inserted into the rear part and should be H05VV-F or H05V-K type. The section to be used will depend on local regulations,
but should not under any circumstances be less than 1 mm².
The cables for wiring the relay contacts should have a section of between 1 mm and 2.5 mm and wire for the one in common should
always have a section of 2.5 mm . Using of halogen- free cables is recommended.
Probes 1 and 2 should be installed as close as possible to the evaporator output. There should not be any device between them (valves,
peep-holes etc.) that could alter the reading.
The controllers are equipped with a port for connection of RS485 (MODBUS) data, which allows for remote management of these
using an AKO-5012 web-server.
IMPORTANT: AKO-14560 controllers can only share a MODBUS network with other AKO-14560 devices. The rest of
AKO devices must be connected to an independent network. For further information, refer to the user manual available
on www.ako.com
+
Mesh
* Select the valve model connected via the EM
parameter.
The table shows the equivalence of terminals for
the most common models.
ºC
%
bar
A+
A-
PRG
SET
B+
B-
Power supply
valve
AKO-D141xx
Description
1
2
3
2: R-404A
4
5: R-717
8: R-HFO1234ze
PRG key
11: R-407F
PRG
UP key
1: The display shows the overheating value.
2: The display shows the suction pressure value (Probe 2).
3: The display shows the valve opening percentage.
4: The display shows the temperature value.
5: An alert is active
6: The display shows the temperature value in ºC.
7: The display shows the suction pressure value in bar
8: The opening degree of the valve has been configured manually
(Cor)
NEVER
be installed in a conduit together with power supply, control or feeder cables.
2
Electronic
expansion
valve*
Tr+
RS485
Tr-
MODBUS
GND
Danfoss
Alco
Carel
Sporlan
ETS
EX5/6
Alco
SEI / SEH
White
White
Yellow
Black
Black
Black
White
White
Red
Brown
Brown
Red
Green
Blue
Green
Green
Liquid
solenoid
valve
Connection/disconnection
should be made via a contact
SET
or potential free relay.
ºC
bar
SET key
SET
DOWN key
2
2
Operation
Keypad
Pressing it for 5 seconds accesses the parameters
PRG
programming menu.
Pressing it twice allows the regulation to be
restarted in the event of an alarm. In the
programming menu, you may return to level 1.
In the programming menu, you may scroll around
the different levels, or during the setting of a
parameter, change its value.
In the programming menu, you may scroll around
the different levels, or during the setting of a
parameter, change its value.
Allows the displayed value to be changed
SET
(overheating, suction pressure, expansion valve
opening or temperature) (only if the DM
parameter = 0).
The programming menu allows you to move
around the different levels and accept changes.
Pressing it for 5 seconds exits the programming
menu.
5
6
7
8