AKO Electronica AKO-14534 Manual - Halaman 2

Jelajahi secara online atau unduh pdf Manual untuk Pengontrol AKO Electronica AKO-14534. AKO Electronica AKO-14534 2 halaman. On/off regulators, 4-20 ma input, 2 relays and acoustic alarm, for moisture, pressure, level, etc

www.ako.com
6- MENUS, PARAMETERS AND MESSAGES
Values in the Def. column are factory-set.
In programming, it must be taken into consideration that the parameters and values dis-
played depend on the option selected in the CFo configuration menu o2C parameter.
Level 1
Menus and Description
Po1 Level 2
R1 Relay Parameter Output
Level 3
Description
di1 R1 and SP1 Differential (Hysteresis)
HL1 Set Point upper limit SP1 of R1
(It cannot be set above this value)
LL1 Set Point lower limit SP1 of R1
(It cannot be set below this value)
HC1 Type of operation R1: (0=Direct) (1=Reverse)
Er1 R1 relay status with faulty sensor: 0=OFF 1=ON
EP Exit to Level 1
Po2 Level 2
R2 Relay Parameter Output
Level 3
Description
di2 R2 and SP2 Differential (Hysteresis)
HL2 Set Point upper limit SP2 of R2
(It cannot be set above this value)
LL2 Set Point lower limit SP2 of R2
(It cannot be set below this value)
HC2 Type of operation R2: (0=Direct (1=Reverse)
Er2 R2 relay status with faulty sensor: 0=OFF 1=ON
EP Exit to Level 1
CFo Level 2
Configuration Parameters
Level 3
Description
R2 Relay output ratio type:
o2C (1=Two independent stages) (3=Neutral Zone)
(2=Two related stages) (4=1 Stage + alarm)
HES Maximum scale value
LES Minimum scale value
bES Blocking the scale between HES and LES
(0=Scale free) (1=Scale blocked)
CAn Sensor calibration (Offset)
rES Display mode:
(0=Integers) (1=One decimal)
toF Delay time for the relays to switch ON
ton Delay time for the relays to switch OFF
EP Exit to Level 1
ALA Level 2
Alarm Parameters
Level 3
Description
ACo Alarm configuration:
(0=Absolute) (1=Related to set point SP1 of R1)
ALt Minimum alarm: (Limited by AHt)
AHt Maximum alarm: (Limited by ALt)
Adi Alarm differential
AdE Alarm delay from the moment at which they must be enabled (min)
Ado Alarm delay at start-up
Optional cancellation of output alarms
AtA by pressing once a key.
(0 = Allows to cancel the output alarms)
(1 = Not allows to cancel the output alarms)
EP Exit to Level 1
InP Level 2
Digital Input Parameters
Level 3
Description
Digital input configuration:
ICF (0=Disabled) (1=External alarm)
(2=R1 Relay set point SP1 variation)
(3=Inversion type of operation HC1)
IPo Digital output status inversion:
(0=Closed Contact) (1=Open Contact)
IdY Digital input enabling delay
USI R1 Relay set point SP1 variation if ICF=2
tSI USI variation length
EP Exit to Level 1
PAr Level 2
General Parameters
Level 3
Description
CYt R1 Relay output switching off frequency
oFt R1 Relay output switching off time
PdE Initial parameters:
(1=YES, configure to "Def" and exit programming)
Ptr Transfer parameters:
(0=Disabled) (1=Send) (2=Receive)
PAS Password to parameters and information
CAd Address for units with communication
PU Programme version (Information)
EP Exit to Level 1
EP Exit programming
MESSAGES
AH The Sensor value exceeds the parameter programmed in AHt
AL
The Sensor value is lower than the parameter programmed in ALt
EAL Active digital input
E1
Sensor failure (Open circuit, crossed, out-of-scale value)
- - - Value > 999
EE
Memory failure
PA Password request to enter programming parameters
NOTE: When the time parameters are modified, the new values are applied when the current
cycle is completed. In order for it to have an immediate effect, switch the controller off and
then on again.
Nos reservamos el derecho de suministrar materiales que
pudieran diferir levemente de los descritos en nuestras Hojas
Técnicas. Información actualizada en nuestra web: www.ako.com.
Values Min. Def. Max.
-50
1
50
LL1 999 999
-999 -999 HL1
0
1
1
0
0
1
Values Min. Def. Max.
-50
1
50
LL2 999 999
-999 -999 HL2
0
1
1
0
0
1
Values Min. Def. Max.
1
1
4
-999 100 999
-999
0
999
0
0
1
-20
0
20
0
0
1
(sec.)
0
0
250
(sec.)
0
0
250
Values Min. Def. Max.
0
0
1
-999 -999 AHt
ALt 999 999
1
1
20
0
0
250
(min)
0
0
250
0
0
1
Values Min. Def. Max.
0
0
3
0
0
1
(min)
0
0
120
-999
0
999
(min)
0
0
254
Values Min. Def. Max.
(h)
0
6
120
(min)
0
0
120
0
0
1
0
0
2
0
0
250
0
0
250
AKO ELECTROMECÀNICA, S.A.L.
D.L.: B - 46.867 - 04
351453252 REV.00
2005
7- PARAMETER TRANSFER
AKO-14918 portable server, with no power supply, in which parameters programmed in a
powered controller can be copied by transfer. Parameters can be transferred again from the
server to other identical powered con-
trollers. Disconnect the unit of the
supply before connecting or discon-
necting the AKO-14918 portable ser-
ver.
To transfer parameters, other servers
are available for controllers that must
be programmed identically in high
quantity without power supply.
8- R1 AND R2 RELAY OPERATION AND CONTROL
SP1 = R1 Relay set point
o2C = 1 Two independent stage
REVERSE operation
HC1 = 1 for R1 Relay
HC2 = 1 for R2 Relay
di1 > 0
di2 > 0
ON
R1
R2
OFF
SP1
SP1+di1
SP2
Start
Stop
Start
di1 < 0
di2 < 0
ON
R1
R2
OFF
SP1-di1
SP1
SP2-di2
SP2
Start
Stop
Start
Stop
o2C = 2 Two related stages
REVERSE operation
HC1 = 1 di1 < 0 SP2 < 0
ON
R2
OFF
SP1-SP2-di1
SP1 - SP2
Start
Stop
ON
OFF
o2C = 3 Neutral Zone
ON
OFF
ON
OFF
o2C = 4 1 Stage + alarm
REVERSE operation
HC1 = 1 for R1 Relay
di1 > 0
ON
R1
OFF
SP1
SP1+di1
VALUE
Start
Stop
di1 < 0
ON
R1
OFF
SP1-di1
SP1
VALUE
Start
Stop
With alarm R2 relay ON
ON
R2
R2
OFF
If ACo = 0
ALt
ALt+Adi
AHt-Adi
AHt
If ACo = 1
SP1+ALt
SP1+ALt+Adi
SP1+AHt-Adi
SP1+AHt
Start
Stop
Stop
Start
ACo is the alarm configuration parameter
9- MAINTENANCE
Clean the controller surface with a soft cloth, soap and water. Do not use abrasive deter-
gents, petrol, alcohol or solvents.
10- WARNINGS
The use of the unit without observing the manufacturer's instructions may alter its safety
qualification.
To ensure correct operation of the apparatus, only sensors supplied by AKO must be used.
Av. Roquetes, 30-38
08812 Sant Pere de Ribes (Barcelona)
AKO-14918
Transfer
SP2 = R2 Relay set point
DIRECT operation
HC1 = 0 for R1 Relay
HC2 = 0 for R2 Relay
di1 > 0
R1
SP2+di2
SP1
SP1+di1
Stop
Stop
Start
di1 < 0
R1
SP1-di1
SP1
SP2-di2
Stop
Start
Stop
DIRECT operation
HC1 = 0 di1 > 0 SP2 > 0
R1
SP1-di1
SP1
VALUE
Start
Stop
R1
R2
SP1
SP1+di1
SP1+SP2
SP1+SP2+di1
Stop
Start
Stop
Start
R1
SP1-di1
SP1
VALUE
Start
Stop
R2
SP1
SP1+di1
VALUE
Stop
Start
DIRECT operation
HC1 = 0 for R1 Relay
di1 > 0
ON
R1
OFF
SP1
SP1+di1
Stop
Start
di1 < 0
ON
R1
OFF
SP1-di1
SP1
Stop
Start
With alarm R2 relay ON
ON
R2
OFF
VALUE
If ACo = 0
ALt
ALt+Adi
AHt-Adi
If ACo = 1
SP1+ALt
SP1+ALt+Adi
SP1+AHt-Adi
Start
Stop
Stop
ACo is the alarm configuration parameter
Tel. (34) 938 142 700 Fax (34) 938 934 054
Apartado (P.O. Box), 5
08800 Vilanova i la Geltrú (Spain)
Power supply
Programming
di2 > 0
R2
VALUE
SP2
SP2+di2
Stop
Start
di2 < 0
R2
SP2
VALUE
Start
VALUE
VALUE
VALUE
R2
AHt
VALUE
SP1+AHt
Start