9 Final Inspection
Gas tightness
− All connections must be gastight. Check the connections for leakage using a leak detector or
spray.
Checking the burner pressure and the line-pressure
− Check whether the burner pressure and the inlet pressure measured agree with the data
indicated on the registration plate
Measuring inlet pressure
− Turn off the gas control tap.
− Open the pressure gauge nipple B (see fig. 1.3) a few turns and connect a pressure gauge hose
to the gas control valve.
− Carry out this measurement when the appliance is on at full gas mark and when it is on the pilot
light.
− If the inlet pressure is too high you are not permitted to connect the appliance.
Measuring the burner pressure:
− Only perform this measurement if the inlet-pressure is correct.
− Open the pressure gauge nipple A (see fig.1.3) a few turns and connect a pressure gauge hose
to the gas control valve.
− The pressure must agree with the value indicated on the registration plate. In case of deviations,
get in touch with the manufacturer.
− * Close the pressure gauge nipples and check these for gas leaks.
Ignition of the pilot light and the main burner
− Start the pilot and main burner according to the instructions in the user's manual.
− Check whether the pilot light is properly and not covered by chips, an imitation log or pebbles.
− Check the ignition of the main burner at full mark or low mark. (The ignition should take place
quickly and easily).
− If the pilot light is extinguished, either intentionally or unintentionally, no attempt should be made
to relight the gas until at least 3 minutes have elapsed.
AKOS Sp. z o o.
ul. Bruszewska 22, 03-046 Warszawa
NIP: 5361925006; REGON 365653140
Tel: +48881697975; email: [email protected]
Table 1 – Deflector state as a function of flue configuration
17 <
<
<
<