Machine screw size #10 hardware is recommended for mounting the ACS. Screw
shafts of at least 2" are recommended. The ACS mounting holes are 3/16" in
diameter, so ensure that the screw heads do not exceed this size. Place
appropriately sized washers between the screw heads and the ACS enclosure
mounting flanges.
Wiring Instructions
Route the ACS conduit to a nearby service panel or junction box. Use the
¼"
included
trade size watertight fitting to provide a moisture-resistant seal with
the service panel or junction box. If necessary, drill a 1/2" diameter hole to
accomodate the liquid-tight fitting or use the included 1/4" NPT to 1/2" NPT
thread reducer kit.
Figure 6. Wiring the ACS in a junction box
Note
Before connecting the ACS service conduc-
tors, please carefully read the section of this
manual titled Service Connections, on page 5.
If you are unsure of the type of power
provided at the service panel, please consult
with your local utility or call your Service
Representative for assistance.
Note
The three ACS service conductors use
stranded 12AWG, 75ºC copper wire. The
insulation of each conductor is color coded
for standard 120VAC installation:
Green: Ground
Black:
Line 1
White: Neutral
Page 9
ACS User's Manual
(120VAC to Ground)