The Neutral at the service panel must be connected to earth ground somewhere
in the system on any of the three connection arrangements. Ground-fault
protection is not possible unless the Neutral (center-tap on the service trans-
former) is connected to an earth ground. If no ground is provided by the
electrical service, a grounding stake must be driven into the ground nearby,
following local electrical codes. The grounding stake must be connected to the
ground bar in the main breaker panel, and Neutral connected to ground at that
point.
Warning Local electrical codes must always be followed when
installing the grounding stake.
The following diagrams illustrate the 3 service transformer secondary connec-
tions most common in the United States.
Figure 2. 220/240V Single Phase
Figure 3. 208V 3-Phase, Wye-Connected
L2 (NOT USED)
L1
120V
NEUTRAL
120V
L2 (NOT USED)
GROUND
L3 (NOT USED)
120V
Page 6
L1
NEUTRAL
GROUND