Installation and Maintenance Instructions for
T400 & T700 ASHCROFT
Switches for Temperature Control
As received, the temperature switch will normally be set to
approximately 90% of the indicated range. After stabilization,
turn the adjustment nut until switch changes mode. Direction of
turning is indicated on a label affixed to the inside of the control
enclosure. When setpoint has been achieved raise and lower
temperature to insure that the setpoint is correct.
After installation of the control replace cover to insure electrical
safety and to protect internal parts from the environment.
Deadband is varied by rotating the wheel on the precision switch.
T450 and T750 VARIABLE DEADBAND SWITCHES
When viewed from the front of the enclosure, rotation
to the left increases deadband – rotation to the right decreased
deadband. Letters on the wheel may be used as a reference.
Deadbands obtainable will vary from 0.5% to 9% of pressure
range depending on range segment.
As received, the temperature switch will normally be set to
ADJUSTMENT OF SETPOINT
approximately 90% of range. Rotate the wheel on the MICRO
SWITCH all the way to the right; this will provide smallest dead-
band. Increase bath temperature to the required setpoint and
turn the adjustment nut until the switch changes mode. Lower
the bath temperature to reset the switch. Rotate the wheel on the
MICRO SWITCH until the desired deadband is obtained. The
upper setpoint will be changing upward with this adjustment.
Lower the bath temperature to reset the switch. Raise the bath
temperature to the desired setpoint and turn the adjusting nut
until the switch changes mode. Lower the bath temperature and
check reset point and deadband.
Route wire leads from switch terminals so as not to interfere with
T428 & T429 MANUAL RESET SWITCHES
or touch reset button.
Note – As indicated above, adjustment of setpoint is made by
use of
⁄
˝ nut. Precision switch element mounting screws and
7
8
bracket adjusting screw are factory sealed and should not be
tampered with.
© 2017 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com