Ashcroft T700 REMOTE MOUNT Petunjuk Pemasangan dan Pemeliharaan - Halaman 2

Jelajahi secara online atau unduh pdf Petunjuk Pemasangan dan Pemeliharaan untuk Beralih Ashcroft T700 REMOTE MOUNT. Ashcroft T700 REMOTE MOUNT 4 halaman. Snap action switches for temperature control

Installation and Maintenance Instructions for
T400 & T700 ASHCROFT
Switches for Temperature Control
There are three holes external to the enclosure for surface
MOUNTING T400 AND T700 SERIES
mounting. Location of these holes is shown on the general di-
mension drawing.
These controls have a
NPT threaded adapter and may be at-
A. Direct - Mounted Controls
1
2
tached directly or indirectly by means of a thermowell to equip-
ment to be controlled. When installing or removing control
always use the wrench flats or hex above the threads. Do
not twist the housing.
Two types of union bushings are available to install a remote
B. Remote Mounted Controls
mounted bulb into a thermowell or other
A non-pressure tight type consists of a bushing, split grommet
and compression nut. To use this, the bulb is inserted through
the nut and the split grommet is slipped into the capillary be-
tween the compression nut and the bushing. After positioning
the bulb as desired tighten the nut to the bushing. This will lock
the capillary at the desired location. The pressure tight type is
clamped to the bulb after insertion by tightening the compression
NC
NO
C
NC
NO
nut. To use
C
this, the union bushing is screwed into the
The compression nut and sleeve are slipped onto the bulb which
is then inserted into the union bushing.
The bulb is then positioned and the compression nut is hand
tightened pus 2
turns. This will lock the capillary at the
1
4
desired location.
Remove cover
ELECTRICAL CONNECTIONS
T400 Series – two screws hold cover to enclosure
T700 Series – cover unscrews
Note – It is recommended that Teflon
CONDUIT CONNECTIONS
used on conduit, bushing or plug threads to ensure integrity of
the enclosure.
T400 Series standard – one
T700 Series standard – two
manent plug. NEMA 7 & 9 enclosures require proper conduit
seals and breathers as per the National Electrical Code.
T400 & T700 series – XJL variation –
bushing supplied.
T400 Series – XJK variation – two
SPDT – Wire directly to the switch according to circuit require-
T400 SERIES
ments. On controls with pilot lights wire lights according to circuit
diagram on inside of cover. See special wiring instruction tag for
single switches with two pilot lights and dual switches with one
or more lights.
© 2017 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M009-10006-10/00 (250-2230G) 12/17
®
Snap Action
NPT threaded hole.
1
2
TERMINAL BLOCK
FRONT SWITCH
TERMINAL BLOCK
REAR SWITCH
NPT threaded hole.
1
2
tape or other sealant be
®
NPT conduit hole right side.
3
4
NPT conduit holes with one per-
3
4
to
NPT reducing
3
1
4
2
NPT conduit holes.
3
4
2-SPDT – Dual switching elements consist of two SPDT switches
mounted together in a bracket. Switches are calibrated to have
simultaneous operation within 1% of range either on increasing
or decreasing pressure but not in both directions. Wire directly to
the front and rear switch according to circuit requirements. Leads
are provided on rear switch color coded as follows:
Common
– White
Normally Closed
– Red
Normally Open
– Blue
When hermetically sealed switch element (s) are supplied, the
lead color coding is as follows:
Common
– White
Normally Closed
– Red
Normally Open
– Blue
SPDT – Wire directly to the switch according to circuit
T700 SERIES
requirements.
2-SPDT – Wire to front switch terminal block (left) and rear
switch terminal block (right) as marked. Strip insulation
insert in proper terminal connector and tighten clamping screw
to secure.
SETPOINT LOCKING SCREW (T400 ONLY)
Once setpoint has been determined, tighten setpoint locking
screw using a
/
˝ allen (hex) wrench. Do not over torque;
5
64
setpoint locking screw only needs to be hand tight.
When performing calibration or changing the setpoint, the setpoint
locking screw should be loosened before turning the setpoint
adjusting nut. Once calibration is complete, re-tighten the set-
point locking screw.
After installation of the control replace cover to insure electrical
safety and to protect internal parts from the environment.
T400 & T700 Series – A single setpoint adjustment nut (
ADJUSTMENT OF SETPOINT
located centrally at the bottom on the inside of the enclosure.
The bulb of the control should be immersed in a bath at the
desired setpoint temperature. Optimum performance will be
obtained if the bulb is fully immersed. Allow five minutes for
initial stabilization.
˝,
5
16
Setpoint
Locking
Screw
˝) is
7
8