Parameter Table
Input Registers
Register-
Protocol-
Name
Adress
Adress
30001
0
Device failure
30002
1
State of device
30003
2
Device flags
Register-
Protocol-
Name
Adress
Adress
32001
2000
Insulating resistance
32002
2001
Asymmetrical
insulating resistance
32003
2002
Measured
mains voltage
32004
2003
Stored min.
insulating resistance
Value
Description
range
0 ... 12
0: No failure
1: Broken wire detection L(+)/L(-)
2: Broken wire detection PE1/PE2
3: Internal failure detected in test mode (Int. 1)
4: Parameter failures (Incorrect setting of
potentiometers on the device)
9: Communication fault Modbus
10: Checksum failure EEPROM (Int. 2)
11: Internal communication fault (Int. 3)
12: Internal error 4 (Int. 4)
0 ... 4
0: Device initialize
1: Device is ready and in measuring mode
2: Device in error mode
3: Device in selftesting
4: Device in advanced test
0 ... 3
Bit 0: Indicator relay K1 energized
Bit 1: Indicator relay K2 energized
Value
Description
range
0 ... 20000,
in 1/10 kΩ
65535
1,2,4
Bit 0: Resistance is asymmetrical
Bit 1: Asymmetrical against L+
Bit 2: Asymmetrical against L-
0 ... 300
in V
without
VSG
0 ... 1000
with VSG
0 ... 20000,
in 1/10 kΩ
65535
15
Data type
Access rights
UINT16
read
UINT16
read
UINT16
read
Data type
Access rights
UINT16
read
UINT16
read
UINT16
read
UINT16
read