The CVX-OPTW is designed to provide isolation between different Wiegand signal
sources.
The CVX-OPTW allows multiple readers and panels to be connected together.
The CVX-OPTW also allows systems with different voltage levels to be electrically
connected together.
The CVX-OPTW may be cascaded to connect additional readers or panels to be
connected.
Data 0 IN
Ground
Data 1 IN
J1 Connector
• Gnd - Input Ground
• Data 0 In - Wiegand Data Input 5- 24 VDC
• Data 1 In - Wiegand Data Input 5 - 24 VDC
J2 Connector
• 5 vdc - Input - regulated 5 vdc @ 30ma
• Pullup +5V - Connection to pullup resistor 1k @ 5VDC
• Data 0 OUT - Open collector Wiegand data output
• Pullup +5V - Connection to pullup resistor 1k @ 5VDC
• Data 1 OUT - Open collector Wiegand data output
• Gnd - Output ground
Notes:
1. Input Ground and Output Ground are electrically isolated.
2. +5VDC (Regulated) is required to operate converter.
+5 VDC
Pullup +5V
Data 0 OUT
Pullup +5V
Data 1 OUT
Ground