5
Technical Specification
Action
Number of pipes
Setpoint Temperature Range
Air connections
Maximum Operating Pipe Pressure
Airflow Usage
Sensitivity
Operating Frequency Band
Battery Life
Operating Conditions
Storage Conditions
Dimensions
Direct / Reverse Acting
Single / Dual pipe
55ºF to 85ºF (13° C to 29 ° C)
Barb fittings, 3/32 in (2.5 mm) ID tube
25 psi (170 kPa)
0.011 scfm (5.2 mL/s)
Factory Adjusted to 2.0 – 2.5 PSI/F
2.4 GHz ISM Band
More than 2 years
(
with four setpoint changes per day
32 to 122ºF (0 to 50ºC)
95%RH Max, Noncondensing
-40 to 122ºF (-40 to 50ºC)
95%RH Max, Noncondensing
Length: 5.6 in (141 mm )
Width: 4.1 in (104 mm )
Depth: 2.1 in (53 mm )
Cypress Envirosystems
198 Champion Court
San Jose, CA 95134, USA
Phone: +1 (408) 943-2800
WPT-DB Installation Manual
Document No. 910-00014-01, Rev. 04
)