Maintenance requirements will vary widely depending on conditions and amount of service.
1. Lubricate seals, bearing surfaces and swivel occasionally with light machine oil or spray lubricant.
2. Check pitot gauge against a test gauge regularly.
ProbleM
1. pitot blade or tip damaged.
2. Leak around lock ring.
3. Leak thru bleeder valve.
4. no reading on
pressure gauge.

MaIntenance

rePaIr
actIon
1.
Replace. instructions and alignment fixture provided with replacement blades.
2. Replace tip o-Ring.
3.
Replace o-Ring.
4. Check for obstruction in
pitot Blade waterway.
Clean coupling and gauge stem. Replace gauge if necessary.