Info codes / alarms

Info codes can consist of up to 4 characters. Each character
has values 0 ... F.
Error in calculator
Error in temp sensor 2
Error in temp sensor 1
Error in flow sensor
Info code
Status of calculator
INT
BIL
INF
Status of temp sensor 2 (return)
INT
BIL
INF
Status of temp sensor 1 (supply)
INT
BIL
INF
Status of flow sensor
INT
BIL
INF
Active info codes are added and displayed simultaneously,
even if it is more than one error.
3 - corresponds to error 2 + 1
5 - corresponds to error 4 + 1
7 - corresponds to error 4 + 2 + 1
9 - corresponds to error 8 + 1
A - corresponds to error 8 + 2
B - corresponds to error 8 + 2 + 1
D - corresponds to error 8 + 4 + 1
E - corresponds to error 8 + 4 + 2
F - corresponds to error 8 + 4 + 2 +1
When any info code is ≥ 8, measurement of energy and vol-
ume stops. Operating time without error stops counting.
When the flow sensor shows error 4 during operation, the time
in the register is counted "flow over q> 1.2 * qs"
Ambiductor AB reserves the right to make changes without prior notice. Reprinting or copying this publication without permission is prosecuted.
Explanation
0 - No error, normal operation
1 - Warning – ending battery life
2 - Temperature difference is greater than the permitted limits
4 - Temperature difference is less than the permitted limits
8 - Electronics failure
0 - No error, normal operation
4 - Short circuit
8 - Sensor failure (open circuit or short circuit)
0 - No error, normal operation
4 - Short circuit
8 - Sensor failure (open circuit or short circuit)
0 - No error, normal operation
1 - No signal, flow sensor is empty
2 - Flow flows in an reverse direction
4 - Flow rate greater than 1.2∙qs (are displayed q=1,2qs)
8 - Electronics failure