Ambirad COBRA CB40 Manuale di installazione, funzionamento, manutenzione e assistenza - Pagina 6

Sfoglia online o scarica il pdf Manuale di installazione, funzionamento, manutenzione e assistenza per Riscaldatore a gas Ambirad COBRA CB40. Ambirad COBRA CB40 19. Gas fired radiant tube heaters

3 Fan assembly
Note: For both horizontal and inclined
mounting the fan assembly must be
perfectly vertical with the fan outlet
facing upwards.
For unflued heaters (UK Only) a fan baffle
must be attached to the fan outlet. (Part
No 201301)
4 Cobra herringbone gas
radiant tube heaters
For herringbone heaters refer to the
relevant information leaflet
(GB/HB/134/0402).
A herringbone system allows several
Cobra heaters to be operated by one
combustion fan. This has the benefit of
only one building penetration being
required when flueing the products of
combustion.
5 Health & safety
Ambi-Rad Limited cannot be responsible
for ensuring that all site safety
procedures are adhered to during
assembly and installation. Sole liability
rests with the installer.
6 Installation - suggested
methods of heater
suspension
Attachment to the heater support lugs
should be made by either a 'speed link', D
shackle, nut bolt and large washer, or in
the case of drop rods, a closed formed
hook. The hanging attachments to
overhead steelwork etc. must be purpose
made to good sound engineering practice
or of a proprietary type fixing. They must
be adequately fixed and designed to carry
the whole weight of the heater, unpacked
152kg.
In the event of suitable roof steelwork not
being available, additional steelwork
should be fitted to enable vertical hangers
to be used for suspending the heaters.
If there are any doubts as to the strength
or suitability of roof steelwork to which
heaters are to be suspended, please refer
to consultant / architect / owner of the
building.
4
7 Minimum mounting heights
and clearances
The recommended minimum mounting
heights, along with the recommended
clearance to combustibles for the Cobra
range of heaters is shown in the table
below.
Clearances 1
Clearances 3
Model
All models
Minimum recommended mounting heights
Model
Horizontal (m)
CB40
Clearance distances
Model
A. Above reflector (fan unflued)
B. Above burner/fan assembly unflued
C & E Beneath tubes
D. To the sides
B. Above reflector and fan outlet flued
F. From ends
All dimensions are in millimetres
Clearances 2
Required angle
Additional chain length (mm)
30˚
45˚
Inclined 30˚ (m)
5.7
5.3
CB40
2300
1300
575
730
Inclined 45˚ (m)
5.3
680
680
500
940