Operation, Maintenance and Installation Manual
INTRODUCTION
®
®
The Flomatic
Flo-Flex
Model 745 Swing Check Valve has been designed to give years
of trouble-free operation during normal operation. This O&M owners' manual will
provide you with the information you need to properly install and maintain the valve and
to ensure a long service life. The Flo-Flex
fluid flow in one direction and closes automatically to prevent back-flow in the reverse
direction (see flow arrow cast into the valve body for flow direction). The Flo-Flex®
Model 745 swing check is design to meet the flange to flange laying length
according to AWWA C508. The valve angled valve seat and fully encapsulated,
resilient disc, is capable of handling a wide range of fluids including flows
containing suspended solids.
Flomatic
®
can provide an optional manual back-flush device that can be installed
on the bottom of the valve to allow manual backflow through the valve in the
reverse direction (Option Model 745 "BF"). Optional Position Indicators (Option Model 745 "PI") PI and Limit Switches
(Option Model 745 "LS") may also be mounted on the valve access cover to provide position indication.
The Valve Size, Flow Direction, Maximum Working Pressure are cast on to the side of the valve body surface for
reference. The "Maximum Working Pressure" is the non-shock pressure rating of the valve at "Max Temperature"
of 140°F (60°C). The valve shall not be subjected to any higher pressure or temperature above the valve
maximum standard rating.

RECEIVING AND STORAGE

Inspect valves upon receipt for damage in shipment. Unload valve carefully to the ground without dropping. Do not allow
lifting slings or chains to come in contact with the seat or flange sealing surface area; use eyebolts or rods through the
flange holes on large valves. Valves should remain crated, clean and dry until installed to prevent weather related damage.
For long term storage greater than six months, the rubber surfaces of the disc should be coated with a thin film of FDA
approved grease such as "Super Lube". Do not expose disc to sunlight or ozone for any extended period as elastomer will
get damaged and degraded.
DESCRIPTION OF VALVE OPERATION
The valve is designed to prevent reverse flow automatically. During system flow
conditions, the movement of the fluid forces the disc to the open position allowing
100% flow area through the valve. The valves rubber coated steel disc
automatically returns to the closed position to prevent reverse flow. Several
optional features are a Backflush device, (Model 745 BF), Position Indicator
(Model 745PI), Limit Switch (Model 745LS). These valve product options are
described in more details below.
Fig 2. Flo-Flex
Cross Section
®
 
®
check valve is opened automatically by the

VALVE CONSTRUCTION

The Flomatic
®
Flo-Flex
of rugged Ductile Iron with a rubber encapsulated valve disc. The rubber coated valve
disc is the only moving part assuring long life with minimal maintenance. The general
Item #
Qty.
1
is
2
3
4
The
5
A/R
6
*Optional EPRM or Viton Coated Steel
®
Flomatic Corp, 15 Pruyn's Island, Glens Falls, New York 12801
Phone: 518-761-9797
®
Swing Check Valve is constructed
Description
Material
1
Body
Ductile Iron
1
Cover
Ductile Iron
1
Disc*
Buna coated Steel
1
Gasket
Buna
Cover Bolt
Steel
1
Plug
Malleable Iron
Fax: 518-761-9798
www.flomatic.com
Standard Max Working Pressure: 
2" thru 24" 250 psi 
Standard Max Temperature: 
140°F (60°C) 
FIG 1. Flo-Flex®
Swing Check Valve
details
of
ASTM
illustrated in Fig. 2. The body (1)
A536
flanged for connection to the
A536
--------
pipeline with an access cover (2).
--------
disc (3) is retained by the cover.
SAE Grade 5
--------
745PI-BF-LS-ASC Rev. B
construction
are
October 12, 2018