CO2 Meter RAD-0002-ZR Manuale d'uso e manuale d'installazione - Pagina 7

Sfoglia online o scarica il pdf Manuale d'uso e manuale d'installazione per Sistema di sicurezza CO2 Meter RAD-0002-ZR. CO2 Meter RAD-0002-ZR 18. Oxygen o2 deficiency safety alarm
Anche per CO2 Meter RAD-0002-ZR: Manuale (7 pagine)

CO2 Meter RAD-0002-ZR Manuale d'uso e manuale d'installazione

Specifications

Measurement Range
Display Resolution
Accuracy
Pressure Dependence
Response Time
O2 AL1
O2 AL2
O2 AL3
Sound Alarm
Warm-Up Time
Power Input
Backup Battery
Relay 1
Relay 2
Relay 3
4-20mA O2
Dimensions
Weight
Temperature
Humidity Range
Storage Temperature
7 | P a g e
R A D - 0 0 0 2 - Z R / M a n u a l a n d I n s t a l l a t i o n
G u i d e
O2 Specification
0-23% display
0.1%
Better than 2%FS
Not pressure dependent
O2: <2min by 90%
19.5% Default (15.5%, 16%, 16.5%, 17%, 17.5%, 18%, 18.5%,
19%, 19.5%, 20%)
16.5% Default (12.5%, 13%, 13.5%, 14%, 14.5%, 15%, 15.5%,
16%, 16.5%)
Default 12.0% (Fixed)
80db@10cm
600 seconds (10 minutes) for full operating temperature range
Monitor Specification
9~32VDC (12~24VDC recommended),2A.
6VDC (5.4V~7.0V), recommended capacity is 12AH
Dry contact relay controlled by AL1 (2Amp) (NO or NC)
Dry contact relay controlled by AL2 (2Amp) (NO or NC)
Dry contact relay (Triggered by power loss to monitor)
O2: Range 0-23%
8.25-inch x 7.8-inch x 3-inch
1.5lbs (Monitor only)
Operating Conditions:
-58°F to 122°F (-50°C to 50°C)
0 ~ 95% RH non-condensing
Storage Conditions:
-4°F to 140°F (-20°C to 60 °C)