Answer J:
The voltage that the phase converter will produce is based off the incoming
single phase voltage. The phase converter will use your voltage measured
leg to leg on single phase as a baseline for balancing the voltage. Leg to leg,
voltage may vary by about 5% while under load. The phase converter does
not transform the voltage up or down. If you need to raise of lower your
voltage, a transformer may need to be added. Please contact American
Rotary for assistance.
Answer K:
Do not measure line to ground. T3, the manufactured line references a
floating ground. The output of a phase converter is a Delta three phase
voltage. If a neutral or 120 volts to ground is needed from all three lines, a
Delta-Wye transformer is needed. American Rotary stocks the correct
transformers for this.
Answer L:
You may need bigger service. Everything may be big enough on your end,
but sometimes the power company's transformer is not big enough. Call your
power company for service.
Answer M:
Blowing a start capacitor is a result of too frequent starts or having a load on
when starting. Make sure all loads are disconnected when starting, including
transformers.
Answer N:
Check and tighten the bolts on the conduit box and all 4 through bolts on
both end bells.
Answer O:
Popping or blowing breakers might mean that there is a short from improper
wiring installation. There may also be grounding connected somewhere that
should not be. Check the phase converter and the idler for both of these
potential problems.
Answer P:
Your breaker may be undersized. Check sizing requirements for your current
setup. If further assistance is needed in sizing, contact American Rotary.