Value
Description (continued)
item
V 7.X
Lev0...
Programming lock:
Lev2
Version display with current input level:
0:
only display of operating parameters, no changes possible
1:
only switching points can be set and "max" and "min" memories
2:
release user level (all operating parameters for customer)
LITH
20... 100
Change display brightness 20... 100% (only for units with dot-matrix display)
AOZS
0... 9999
Scale the analog output - start value (e. g. 0 bar = 4 mA)
(only
V 7.X)
AOFS
0... 9999
Scale the analog output - end value (e. g. 400 bar = 20 mA)
((output signal start value always corresponds to the display initial value,
e. g. 0 bar = 4 mA), max. turn-down 4: 1, i. e. at values below 25 % of the
measuring
range the analog output is switched off
Code
000... 999
Enter the code level:
Lev1:
471
Lev2:
740
Lev0:
999
OPT
-----
Display of the unit options stored by the manufacturer Barksdale.
(only
V 7.X)
12
Changes:
(up + down 5 seconds) Lev1 - Lev0
(up + down + M 5 seconds) Lev2 - Lev0
Operating Instructions
Dual Pressure Switch UDS 7
Dual Temperature Switch UTS 7
1
Intended Applications ................................................................................................. 2
2
Safety Instructions ...................................................................................................... 2
3
Standards ..................................................................................................................... 3
4
Warranty/Guaranty ...................................................................................................... 3
5
Installation/Commissioning ........................................................................................ 4
6
Maintenance/Cleaning ................................................................................................. 5
7
Technical Data ............................................................................................................. 6
8
Operation ..................................................................................................................... 8
9
Programming ............................................................................................................... 9
10
User Level Dialog ...................................................................................................... 10
Barksdale GmbH
Dorn-Assenheimer Straße 27
D-61203 Reichelsheim
Phone:
+49 (6035) 949-0
Fax:
+49 (6035) 949-111 and 949-113
email:
Internet: www.barksdale.de
Art. no. 923-1724
Index E, 19.08.2009
Software version: from V 1.X
Specifications are subject to changes
without notice!
1