Domus Ventilation DX12 Manuale di installazione e manutenzione - Pagina 3
Sfoglia online o scarica il pdf Manuale di installazione e manutenzione per Ventilatore Domus Ventilation DX12. Domus Ventilation DX12 7. Fan module 50hz/60hz
Installation and Maintenance
DX Fan Module 50Hz/60Hz
4.1.4 Supply / Extract Fan Operated via remote DX-CON Control
Double
Fuse
pole
max.
isolator
3 amp
L
N
mains
supply
DX-CON cont roller
Remote switch may be set: On/Off, Supply/ Extract, Economy/Std.
(variable speed), Auto/Manual.
4.1.5 Supply / Extract Fan Operated via remote DX-CON Control
and Remote Sensor(s)
Double
Fuse
pole
max.
isolator
3 amp
L
N
mains
supply
DX-CON cont roller
Remote switch may be set: On/Off, Supply/ Extract, Economy/Std.
(variable speed), Auto/Manual.
One or more Remote Sensors may be wired in parallel to one DX-CON
Control.
Humidity Sensor: DX-RH
4.1.6 Supply / Extract Fan Operated via remote DX-CON Control
and an Integral Sensor
Double
Fuse
pole
max.
isolator
3 amp
L
N
mains
supply
DX-CON cont roller
Remote switch may be set: On/Off, Forward/Reverse, Economy/Std.
(variable speed), Auto/Manual.
Maximum one Integral Sensor per fan, 6/9/12 denotes unit size identity.
Humidity Sensor: DX-H6/9/12
Run-On Timer : DX-T6/9/12
Passive Infra Red Sensor: DX-PIR6/9/12
A single sensor will switch all fans if more than one fan is being
operated by a single DX-CON controller.
NOTE: Multi-fan options:
Up to 5 fans (size 6"/9") can be controlled by one DX-CON.
Up to 2 fans (size 12") can be controlled by one DX-CON.
Do not mix different fan sizes on the same controller.
LAB1346R May 2018
L4
L3
L2
L1
L1
N
N
Remote sensor
L2 L1 N
L4
L3
L2
L1
L1
N
N
Required if using
integral Timer
L4
L3
L2
L1
L1
N
N
DX Fan unit with
integral sensor
4.2 Unit Consumption & Weight
L5
L4
Model
L3
L2
DX6 supply & extract
L1
N
DX9 supply & extract
DX12 supply & extract
DX Fan unit
Note figures are for extract only at 50hz.
4.3 Electrical Specification
230V ~ 50Hz / 220V ~ 60Hz Class I. Motor thermally protected by
overload device. Cable: 1mm max. or min. Fuse: 3 amp (if fan is supplied
from a 5A lighting circuit, no local fuse is required).
Note: If 2 x 12 inch fans or 5x 6 or 9 inch fans are used in the same
operating mode in the same room they should all be controlled from
L5
the same DX-CON speed control. This avoids the possibility of one fan
L4
(if speed controlled at a lower flow rate) being stalled by the other
L3
fan(s).
L2
L1
Adequate make-up air provision sufficient to provide ventilation in
N
accordance with building regulations is required in all rooms. This
should be checked during commissioning with all fans in the same room
running together in all possible configurations.
DX Fan unit
The automatic shutters, motor bearings should be frequently inspected
and maintained to ensure they open fully/operate satisfactorily. Use of
an RCD and fused spur with 1A, Bussmann TDC180, BS1362, fuse
(Farnell order no: 1123029) for 1 fan or 2A, Bussmann TDC180, BS1362
fuse (Farnell order no: 1123032) for 2 or 3 fans is recommended.
Always confirm airflow direction before commissioning.
L5
L4
L3
L2
L1
N
V E N T I L A T I O N
Input Power
Weight
(W)
(kg)
Max.
Economy
38
20
4.1
50
37
5.7
100
70
8.6