Domus Ventilation Sapphire DME100C Centrifugal dMEV Istruzioni per l'installazione
Sfoglia online o scarica il pdf Istruzioni per l'installazione per Ventilatore Domus Ventilation Sapphire DME100C Centrifugal dMEV. Domus Ventilation Sapphire DME100C Centrifugal dMEV 2. Extractor fans
V E N T I L A T I O N
OPERATION
Overrun timer boost adjustment
Before making any adjustments, isolate the fan from the power supply. Remove the front cover and the
body moulding. Locate the 'jumper' on the relevant set of pins to achieve the desired run-on time (see
Diagram 4).
Humidity boost adjustment
All humidistat dMEV's automatically sense a rapid change in humidity and adjust accordingly. The
humidity control does not require manual adjustment. Humidistat dMEV's, when energised for the first
time, will run and time out as part of the stabilising process.
Performance:
Position jumpers for desired trickle and boost performance
Trickle
Position 1
4 l/s
•
Position 2
5 l/s
•
Position 3
6 l/s
•
Position 4
7 l/s
•
Boost
Position 5
Wet room - through wall
•
Position 6
Kitchen – through wall
•
Position 6
Wet room – in room
•
Position 7
Kitchen – in room
•
Position 8
Boost 18 l/s
•
Rating:
230 V 50 Hz IPX4
This product is double insulated and does not require an earth conductor.
Maximum room temperature 40ºC
V E N T I L A T I O N
Domus Ventilation
Cambria House
Caerphilly Business Park
Van Road
Caerphilly
CF83 3ED
Tel: +44 (0)3443 715523
Fax: +44 (0)3443 715524
Email: [email protected]
www.domusventilation.co.uk
LAB1110R
Issue 4
09/17
Installation Instructions
4
LAB1110R
Issue 4
09/17
V E N T I L A T I O N
Sapphire Range
Centrifugal dMEV