Purpose
Since the installed supply conditions may be different from those applied in the factory, it is
appropriate at commissioning to carry out some simple checks and tests of the product.
Procedure
Check that:
a. the designation of the mixing valve matches the intended application.
b. the supply pressures are balanced and within the range of operating pressures for the
designation of the valve.
c. the supply temperatures are within the range of 55 - 65 °C for the valve for the prevention
of legionella etc.
Note: the final stabilised mixed water temperature during installation should not exceed the
values in table 3. if there is residual flow during the commissioning or the annual verification
(cold water supply isolation test), it is acceptable providing the temperature of the water
seeping from the valve is no more than 2 °C above the designated maximum mixed water
outlet temperature setting of the valve. temperature readings should be taken at the normal
flow rate after allowing for the system to stabilise.
Maximum Temperature Setting
the maximum blend temperature obtainable by the user should be limited to prevent
accidental selection of a temperature that is too hot.
make sure that an adequate supply of hot water is available at the hot inlet of the mixer.
the minimum temperature of the hot water must be at least 10 °C above the desired blend.
However, during resetting, this should be close to the typical storage maximum to offset
the possibility of any blend shift due to fluctuating supply temperatures. make sure that
both inlet isolating valves are fully open. temperatures should always be measured using a
thermometer with proven accuracy.