Sfoglia online o scarica il pdf Manuale di avvio rapido per Alimentazione bolid RIP-12. bolid RIP-12 8.

2. Press on the notches and open the cover
Figure 1. Top View
WARNING!
While connecting mains power wires 220 V to the input terminal block, please
observe correct polarity of connecting the Line and Neutral circuits. Connect the
circuits to the RIP as shown in Figure 3.
Figure 3. RIP-12 mod.14 (RIP-12-2/7P2-R) Connection Diagram
2.2.5 Following are the recommended cross section areas of the wires to be connected to
the RIP:
1) To connect the RIP to mains power 220 V (the XT3 terminal block): 0.75...2.5 mm
for stranded wires or 1...2 mm in diameter for solid wires;
2) To connect the load: 0.5...2.5 mm
solid wires taking into account the maximum voltage drop on wires at maximum load
current (the minimum allowable voltage at the load).
2.2.6 If several load circuits are to be connected, it is recommended to use Bolid
manufactured BZK rev.01 power distribution module.
2.2.7 The tamper switch of the RIP can be used to mute the buzzer.
4
1
2
for stranded wires or 0.8...2 mm in diameter for
Figure 2. Overall and Mounting Dimensions
90
90
165