Charging Level Indicator
RED LED shows that the battery is in the initial charging phase.
100%
YELLOW LED shows that the battery charger has reached 80% of charge.
80%
80%
GREEN LED shows that the battery has reached 100% of charge.
START
Further information can be found in the description of the Charging Curve.
Line Alarm Indicator
This RED LED turns on when there is a phase missing on the mains.
In this situation the battery charger will not operate and the charging level indicator
changes to yellow.
LINE
(Check mains and input fuses).
ALARM
Alarms (Two-tone audible message)
An two-tone audible message and the flashing LED shows that an Alarm situation has occurred:
Condition
Audible message +
RED flash
Audible message +
YELLOW flash
Audible message +
GREEN flash
Audible message +
RED-YELLOW flash
Audible message +
RED-GREEN flash
Audible message +
YELLOW -GREEN flash
Audible message +
RED-YELLOW-GREEN
flash
When there is an alarm the battery charger stops supplying current.
Thermal Sensor and/or External Indicator
Thermal Sensor and External Indicator are Options that have to be connected to the 5 poles socket 180° .
Battery charger CHFC5-7-9
Alarm Type
Battery Presence
Thermal Sensor
Timeout
Battery Current
Battery Voltage
Selection
Thermal
Unless otherwise stated, the compensation of the Battery Voltage in function of
the temperature of the Thermal Sensor is of -5mV/° C for battery cell.
The control range of the Thermal Sensor goes from -20° C to +50° C.
The External Indicator reflects exactly the LED Indicator which is placed on the
equipment.
Further information can be found in the description of the Charging Curve.
Description (Action)
Battery disconnected or not in conformity. (Verify the
connection and the nominal voltage).
The thermal sensor is disconnected during the re-
charge or it is out working range. (Verify the
connection of the sensor and measure the temperature
of the battery).
Phase 1 and/or Phase 2 have a duration in excess of
the maximal allowed. (Verify the battery capacity).
Loss of output Current control. (Failure of the control
logic).
Loss of output Voltage control. (Battery disconnected
or failure of the control logic).
An unavailable configuration has been selected (Verify
the selector's position)
Overheating of semiconductors. (Verify the fan
operation).
5