Akytec MV110-16DN Manuale d'uso - Pagina 13

Sfoglia online o scarica il pdf Manuale d'uso per Unità di controllo Akytec MV110-16DN. Akytec MV110-16DN 19. Analog input module, 16 channel

Akytec MV110-16DN Manuale d'uso

Factory settings restoration

7. Factory settings restoration
If the communication between the module and PC cannot be established and network
parameters of the module are unknown, the default network settings should be restored.
The following steps are required:
Turn off the power supply
Remove the front cover of the module
Insert the jumper X2. Module will operate with the default network parameters, the
user settings remain stored.
Turn on the power supply again
Dangerous voltage
Electric shock could kill or seriously injure.
WARNING
The voltage on some components of the circuit board can be danger-ous! Direct
contact with the circuit board or penetration of a foreign body in the enclosure
must be avoided!
Run M110 Configurator
In the window 'Connection to device' enter the values from the Table 7.1 or click the
key 'Use factory settings' (see Fig. 7.1)
Click 'Connect' to establish the connection with factory settings
The main window of the Configurator opens. Saved user parameters of the module
can be read now (see Fig. 7.2).
Open folder 'Network parameters' and note the user network parameters
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
Fig. 7.1 Start window of configuration software
12