DOTECH FX3D Manuale d'uso - Pagina 3
Sfoglia online o scarica il pdf Manuale d'uso per Regolatore di temperatura DOTECH FX3D. DOTECH FX3D 4. Digital temp controller
Parameter
Temperature Setting Group
FX3D
OUT1
OUT2
Push for 3 sec.
Output #1 setup value
ST 1
Output #2 setup value
ST 2
Temperature Setting Group
No
Menu
4 0001
Output #1 setup value
4 0002
Output #2 setup value
Setting 1 Group
(PRG Button Push for 5 Sec.)
No
Menu
4 0003
Select Control Type
4 0004
Control Deviation Value
4 0005
ON Delay Time
4 0006
Minimum OFF Time(※1)
Output
#1
4 0007
Minimum ON Time(※2)
4 0008
Deviation Type(※3)
4 0009
Set Value Max.
4 0010
Set Value Min.
4 0011
Select Control Type
4 0012
Control Deviation Value
4 0013
ON Delay Time
4 0014
Minimum OFF Time(※1)
Output
#2
4 0015
Minimum ON Time(※2)
4 0016
Deviation Type(※3)
4 0017
Set Value Max.
4 0018
Set Value Min.
※1) Min OFF Time : It doesn't make it output within Min. OFF Time after output is OFF . During Min OFF Time, output lamp is turned on with output after it ickers every 1 second intervals.
※2) Min ON Time : It is for avoiding frequent ON/OFF of control output and maintains ON condition in spite of OFF condition during Min ON Time after being turned on.
※3) Select Deviation Type : It selects deviation type. e.g) Condition (Cooling, Setup value 10.0, Deviation 1.0)
In case of +deviation -> Operate at ON (11.0) / OFF (10.0) In case of ±deviation -> Operate at ON (10.5) / OFF (9.5)
Setting 1 Group
T Y 1
D F 1
0.0
D T 1
F T 1
N T 1
T P 1
T Y 2
0.0
D F 2
(SEL Button Push for 3 Sec.)
Code
Unit
ST1
ST2
Code
Unit
OFF (0) : Display C (1) : Cooling mode H (2) : Heating mode
TY1
DF1
Sec
DT1
Sec
FT1
Sec
NT1
TP1
UH1
UL1
OFF (0) : Display C (1) : Cooling mode H (2) : Heating mode
TY2
DF2
Sec
DT2
Sec
FT2
Sec
NT2
TP2
UH2
UL2
Run Mode
Push
Push
for 3 sec.
for 5 sec.
Select Control Type #1
Control Deviation Value #1
ON Delay Time #1
Minimum OFF Time #1
Minimum ON Time #1
Select Deviation Type #1
Select Control Type #2
Control Deviation Value #2
Menu move
Setup value
Step
Min
°C
0.1
UL1
°C
0.1
UL2
Step
Min
°C
0.1
0.1
1
1
1
P (0) : Deviation
PN (1): ± Deviation
°C
1
UL1
°C
1
SL
°C
0.1
0.1
1
1
1
P (0) : Deviation
PN (1): ± Deviation
°C
1
UL2
°C
1
SL
- 3 -
Setting 2 Group
Run Mode
Push
for 10 sec.
L O C
Select Lock Function
I N
Select Sensor Type
S H
Max. Sensor Input Range
S L
Min. Sensor Input Range
U N T
Display Unit
D P
Decimal Point Display
Menu move
Max
Default
0.0
UH1
0.0
UH2
Max
Default
C (1)
999.9
1 .0
0
999
1
0
999
0
0
999
5
P
SH
1 00
UH1
-45
C (1)
999.9
1 .0
0
999
2
0
999
0
0
999
5
P
SH
1 00
UH2
-45
Push
for 3 sec.
Setup value
Custom Setup
Custom Setup
R20150924