DOTECH EVC10B-T-00 Manuale d'uso - Pagina 6

Sfoglia online o scarica il pdf Manuale d'uso per Controllore DOTECH EVC10B-T-00. DOTECH EVC10B-T-00 8. Electronic expansion valve controller

DOTECH EVC10B-T-00 Manuale d'uso
: Setting 2 group table (Menu 2 =
Address
Description
4 0061
Password
4 0062
Type of refrigerant
4 0063
Pressure sensor Max. range (at 4.5V)
4 0064
Pressure sensor Min. range (at 0.5V)
4 0065
Pressure sensor offset correction
4 0066
Temp. sensor offset correction
4 0069
Jerk control ratio ※4
4 0070
Expansion valve open ratio upper limit
4 0071
Expansion valve open ratio lower limit
4 0072
EEV compulsory open ratio
4 0073
Sensor input filter time
4 0076
Display mode
4 0077
Run/Stop method
4 0078
Communication ID setup
4 0079
Communication speed (BPS) setup
Initialization
※1 Password
It is necessary to input password to change or initialize parameters and default
value is "5". Be sure to take notes not to forget or loss it after changing
password.
※2 Setup max. and min. range of pressure sensor
Setup max. and min. range of pressure sensor. Pressure sensor is a ratiometric
type of 0.5~4.5V. Default value before shipment is 1~15bar.
※3 Setup pressure sensor offset correction
Users can input offset correction value for pressure sensor, temperature sensor
and input error. It was set 0.0 as a default value.
※4 Jerk control ratio
Limit value of motor speed variation (Jerk Control)
※5 Expansion valve compulsory open ratio
If users want to temporarily control expansion valve by designated open ratio
while controlling normally. Default value before shipment is OFF.
: Setting 2 group table (Menu 3 =
Address
Description
4 0042
Expansion valve excitation type
4 0043
Expansion valve TOTAL PULSE
4 0044
Expansion valve OPEN PULSE
4 0045
Expansion valve DRIVE SPEED (PPS)
※ Users should input parameter which is suitable for characteristic of expansion valve. In case of difference,
it may be caused by malfunction or valve and system will be damaged.
2.PR
)
Code
PCD
22(0)= R22
RFY
134(1)= R134A
PSH
PSL
PCR
TCR
JEY
OPH
OPL
O 11
UCR
0= 1~4 Rotation
1= Superheat
D I S
2= Evaporator outlet pressure
RMT
ID
BDR
RST
3.PR
)
Code
EVD
EVP
EVO
10(0)= 10PPS
20(1)= 20PPS
EVS
30(2)= 30PPS
Unit
Step
-
1
404(2)= R404A
407(3)= R407C
bar
1
bar
1
K
0.1
K
0.1
0.1
%
1
%
1
-
0.1
%
0.1
0= Always run
1= Digital input(RUN)
-
1
48(0)= 4800
96(1)= 9600
-
1
※6 Sensor filter input time
Only expert can setup this parameter. If sensor input is excessively unstable,
increase filter value and make it stable.
※7 EEV compulsory open ratio
It can be used to temporarily control electronic expansion valve with designated
open ratio when controlling normally.
Default value is set as not in use.
※8 Way to change of display mode
Press up / downward button to change parameters
(DIS parameter will be changed)
Parameter number will be displayed for one second before parameter is
displayed.
* It is possible to change with direct input when displaying superheat set point.
※9 Initialization
If password is entered, parameters will be initialized as an default value before
shipment.
Unit
Step
1-2 = 1-2 phase excitation
PULSE
1
PULSE
1
50(3)= 50PPS
80(4)= 80PPS
-6-
Min.
Max.
0
999
410(4)= R410A
23(6)= R23
717(5)= R717
507(7)= R507C
-1
99
-1
99
-9.9
9.9
-19.9
19.9
0.1
100.0
0
100
0
100
0.1
10.0
0.0
100.0
3= Expansion valve open ratio
4= Evaporator outlet temperature
5= Saturation temperature
2= Communication Run
1
254
192(2)= 19200
384(3)= 38400
0
999
Min.
Max.
2 = 2 phase excitation
100
999
0
999
100(5)= 100PPS
250(7)= 250PPS
200(6)= 200PPS
500(8)= 500PPS
Default
Custom
5
22(0)
15
-1
0.0
0.0
100.0
100
0
1.0
OFF(-1)
1
1
1
96
0
Default
Custom
2
200
100
200
EVC10B R20140821