4.3.3.3 Minimum Pulse Duration
The minimum pulse duration defines the minimum time, the switching signal of the related SSC stays active
or inactive after the change of its status.
When to apply?
To align the timing of the sensor to a slower PLC.
-
To avoid bouncing.
-
To avoid false pulses due to short losses of a proper signal.
-
To straighten the clock / pace
-
Parameter name
Minimum Pulse Duration.SSC1 Time
en_BA_O200_IO-Link_V1.docx
15.08.2018/
Figure 20 Minimum Pulse Duration
Short Description
Sets the response delay time,
Available for SSC1 and SSC4
17/34
Rights
Unit / Allowed
values
rw
0 to 60.000 ms
Baumer Electric AG