Baumer GBMMW Manuale - Pagina 15
Sfoglia online o scarica il pdf Manuale per Convertitore multimediale Baumer GBMMW. Baumer GBMMW 41. Absolute encoder with powerlink interface
Anche per Baumer GBMMW: Manuale (19 pagine), Manuale (26 pagine), Manuale (24 pagine), Manuale (19 pagine)
5.5.3.
Clock synchronisation
Clock-synchronous operation is activated by a tick on "SynchronizeDP-Slave at equidistant DP-cycle".
Time Ti marks the time before the equidistant bus clock (Global Control Message, GC) where the encoder is
sensing the position data with micro-second precision. It should be aimed at the smallest possible value.
250 µs minimum is admissible if encoder operation is without scaling, i.e. always with the maximum
resolution. For enabled scaling the minimum value is 375µs. In case several clock-synchronous DP-slaves
exist in the bus that require more time for data evaluation automatically the maximum value will be utilized.
Time To is insignificant to the encoder. Usually the projecting software makes a proposal under consideration
of correlations to other bus parameters.
Manual_ProfibusDPV2_BIDE_EN.docx
15/41
Baumer IVO GmbH & Co. KG
22.11.12
Villingen-Schwenningen, Germany