Baumer Hubner Berlin microGen PMG10 Manuale operativo - Pagina 26

Sfoglia online o scarica il pdf Manuale operativo per Convertitore multimediale Baumer Hubner Berlin microGen PMG10. Baumer Hubner Berlin microGen PMG10 40. Absolute encoder
Anche per Baumer Hubner Berlin microGen PMG10: Manuale operativo (44 pagine), Manuale operativo (40 pagine)

6
|
Electrical installation
6.2.2

Output signals additional incremental output (optional)

At positive rotating direction
A+
A-
B+
B-
R+
Zero pulse+
R-
Zero pulse-
Ill. 15: Output signals with positive direction of rotation (zero pulse R+ and R- are only available at addi-
tional output II)
6.2.3

Switching level additional output incremental (optional)

Switching level
High/Low
Transmission length
Output frequency
I
The TTL/HTL output (Vin = Vout) at the additional output II incremental is galvanically iso-
lated and requires a separate voltage supply.
Tab. 2: Switching level additional output incremental (optional)
6.2.4

Programming interface (only for programmable variant)

Encoder parameters such as additional output, switch-off and switch-on speeds or also the
switching hysteresis can be changed and read out via connection SA and SB. The Z-PA.SDL1
WLAN adapter can be used for encoder access via web browser.
Also see about this
2 Z-PA.SDL.1 WLAN adapter: Programming device for HMG10P/PMG10P [} 30]
6.2.5

LED activity indicator

LED
INC1
INC2 (additional output incre-
mental
Status
Speed
Tab. 3: LED activity indicator
26
90°
TTL/RS422
≥ 2,5 V / ≤ 0,5 V
≤ 550 m bei 100 kHz
≤ 600 kHz
red
No function
Undervoltage
n
Overload
n
Excess temperature
n
Internal error
Speed higher than switching
speed (overspeed)
Operating Manual
Baumer Hübner
TTL/HTL (Vin = Vout)
≥ 2,5 V / ≤ 0,5 V (TTL)
n
≥ Ub − 3 V / ≤ 1,5 V (HTL)
n
≤ 550 m bei 100 kHz (TTL)
n
≤ 350 m bei 100 kHz (HTL)
n
≤ 600 kHz (TTL)
n
≤ 350 kHz (HTL)
n
green
No function
OK
OK
Speed below switching speed
PMG10 & PMG10P Profibus DP | V1
I