Setup: Program Mode

PROGRAM MODE
Allows output relays to be grouped, with each group
controlled by a switch input.
To Use Program Mode:
1. Make sure the output relays are properly connected to the output
terminals and that the group switches and/or timer outputs are
properly connected to the input terminals.
2. Make sure NORMAL MODE is selected. The top indicator LED of
the NORMAL MODE select button should be ON.
3. Use the INPUT SELECT button to scroll to the desired input #1-5
(when its indicator INPUT LED is ON).
4. Press the PROGRAM MODE select button. Its indicator light will
begin flashing. The OUTPUT LEDs of the relays that are controlled
by the selected input will be ON.
5. Add or remove output relays from the selected input by pressing
the OUTPUT button of the desired relay.
6. When you have selected all the relays for the group, press the
NORMAL MODE select button to return to NORMAL mode.
7. Repeat steps #3 - 6 to program other inputs with a relay group.
NOTE: A relay can be in more than one group.
8. When you are programming a relay group, you can include or
exclude all the output relays by pressing the ON OVERRIDE or OFF
OVERRIDE button, respectively.
9. When you are in NORMAL mode, you can turn all the relays
assigned to an input ON or OFF by selecting that input with the
INPUT SELECT button, and then pressing the ON OVERRIDE or
OFF OVERRIDE button.
NOTE:
If there is 2 minutes of inactivity during
PROGRAM mode, the scanner will revert to
NORMAL mode.
To return to PROGRAM mode, press the
PROGRAM MODE selectbutton.
WRS-2224: Directions & Applications
Output
Buttons
page 7
Output
LEDs
Program Mode
Select Button
Normal Mode
Select Button
ON Override
Select Button
OFF Override
Select Button
Input
Select Button
Input
Terminals
Input
LEDs
DOUGLAS
lighting controls