Baumer NE210 Manuale di istruzioni per l'uso - Pagina 28

Sfoglia online o scarica il pdf Manuale di istruzioni per l'uso per Sportello di cassa Baumer NE210. Baumer NE210 44. Electronic preset electronic preset counter

Baumer NE210 Manuale di istruzioni per l'uso
NE210
voltage selector
6
5
28
3.1

Connecting the voltage supply

Three voltage supply are available:
AC voltage: 24/48 VAC (50/60 Hz), set the required alternating vol-
tage with the voltage selector switch.
AC voltage: 85...265 VAC (50/60 Hz), wide range supply
DC voltage: 24 VDC ±10 %
Supply voltage
24 VAC ±10 %
48 VAC ±10 %
85...265 VAC
24 VDC ±10 %
➜ Model 24/48 VAC: set the required alternating voltage with the
voltage selector switch.
➜ Connect AC at the contacts 2 and 3 according to the terminal
diagram.
DC-voltage 24 VDC
Connect voltage supply that is free from any interference. Do not uti-
lize the voltage supply for parallel supply of drives, shields, magnetic
valves, etc. Supplying lines must be separated from lines providing
load current.
Fire protection: Operate the instrument using the recommended
external fusing indicated in the type label. EN 61010 specifies that 8
A/150 VA (W) must never be exceeded in the event of a fault.
3.2
Assignment signal output „relay contact"
Terminals 4, 5 and 6 form a no-potential changeover contact, which
can be assigned as a pulse or continuous contact in accordance
with the adjoining wiring diagram.
Implementation as a pulse or continuous signal is effected via DIP-
switch 2 and in the programming mode, line 12 (see 3.6).
4
The pulse time is programmed in the programming mode, line 2.
Max. rating
150 VA/30 W
The user is responsible for ensuring that a switching load of 8A /
150 VA (W) is not exceeded in the event of a fault. Internal spark
suppression by means of two zinc oxide varistors (275 V). The output
relays of the instrument (1 relay or several) may only be disengaged
in total 5 x per minute at the most. Admissible clicks according to
interference suppression standard EN 61000-6-4 for the industrial
sector. In case of a higher switching rate, the operator must take
care of interference suppression on the spot and under his own
responsibility by observing the load to be switched.
➔ Assign terminals 4, 5 and 6 (relay contact outputs) accordingly.
www.baumer.com
Recommended external protection
M 400 mA
M 400 mA
M 315 mA
M 400 mA
Max. voltage
250 V
Max. current
1 A